User manual

Sensorsoft Alert User Manual
ssTrapOnScalarWarningInterval
DESCRIPTION
: The time interval in minutes between traps when the agent detects that the
currently indexed variable on the currently indexed device enters a Breach of Warning High Limit
status or Breach of Warning Low Limit status.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.35.0
Non-volatile
ssTrapOnBooleanCriticalEnable
DESCRIPTION
: A zero value disables this trap. A value of one enables this trap. When enabled,
this trap is sent when the agent detects that the currently indexed variable on the currently indexed
device enters a Breach of Boolean Critical Limit status. It will be sent periodically using the time
interval in minutes specified by ssTrapOnBooleanCriticalInterval.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.36.0
Non-volatile
ssTrapOnBooleanCriticalInterval
DESCRIPTION
: The time interval in minutes between traps when the agent detects that the
currently indexed variable on the currently indexed device enters a Breach of Boolean Critical
Limit status.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.37.0
Non-volatile
ssTrapOnReturnToNormalEnable
DESCRIPTION
: A zero value disables this trap. Any other value enables the trap. When enabled,
this trap is sent only once.
TYPE
: Integer
ACCESS
: Read/Write
OID
.1.3.6.1.4.1.15848.1.38.0
Non-volatile
ssEmailOnScalarCriticalSubject
DESCRIPTION
: This is the subject line of the email that will be sent when the currently indexed
variable on the currently indexed device enters Breach of Critical High Limit status or Breach of
63