User manual
Sensorsoft Alert User Manual
ACCESS: Read Only
OID
.1.3.6.1.4.1.15848.1.20.0
ssVarStatus
DESCRIPTION
: The status of the currently indexed variable. The status can be: Normal, Breach
of Boolean Critical Limit, Breach of Critical High Limit, Breach of Critical Low Limit, Breach of
Warning Low Limit, Breach of Warning High Limit and Returned to Normal status.
TYPE
: String
ACCESS
: Read Only
OID
.1.3.6.1.4.1.15848.1.21.0
ssScalarData
DESCRIPTION
: The device's data, if the currently indexed variable on the currently indexed
device is of the scalar class.
TYPE
: Integer
ACCESS
: Read-Write
OID
.1.3.6.1.4.1.15848.1.22.0
ssApplianceOfMeasure
DESCRIPTION
: The appliance of measure for the scalar data. For example, if the currently
indexed variable is a temperature reading, then the appliance of measure will be either F for
Fahrenheit or C for Celsius. Boolean variables do not have appliance of measure.
TYPE
: String
ACCESS
: Read Only
OID
.1.3.6.1.4.1.15848.1.23.0
ssScalarCriticalHighLimit
DESCRIPTION
: If the currently indexed variable is of scalar class, then this represents the limit
that the scalar data must reach, or rise above, before this variable enters Breach of Critical High
Limit status.
TYPE
: Integer
ACCESS
: Read-Write
OID
.1.3.6.1.4.1.15848.1.24.0
Non-volatile
ssScalarWarningHighLimit
DESCRIPTION
: If the currently indexed variable is of scalar class, then this represents the limit
that the scalar data must reach, or rise above, before this variable enters Breach of Warning High
status.
TYPE
: Integer
60