User manual
Sensorsoft Alert User Manual
To enable a specific alert action for a particular alert state, the corresponding ssXXXXXXEnable MIB
object must be set to 1. The following chart lists the ssXXXXXXEnable objects that correspond to each
alert action for each alert state:
Alert State Trap Enable Object Email Enable Object
Command Line
Enable Object
Breach of
Critical High
Limit
SsTrapOnScalarCriticalEnab
le
SsEmailOnScalarCriti
calEnable
ssCommandOnScalar
CriticalHighEnable
Breach of
Warning High
Limit
SsTrapOnScalarWarningEna
ble
SsEmailOnScalarWar
ningEnable
ssCommandOnScalar
WarningHighEnable
Return To
Normal
SsTrapOnReturnToNormalE
nable
SsEmailOnReturnToN
ormalEnable
SsCommandOnReturn
ToNormalEnable
Breach of
Warning Low
Limit
SsTrapOnScalarWarningEna
ble
SsEmailOnScalarWar
ningEnable
ssCommandOnScalar
WarningLowEnable
Breach of
Critical Low
Limit
SsTrapOnScalarCriticalEnab
le
SsEmailOnScalarCriti
calEnable
ssCommandOnScalar
CriticalLowEnable
For instance, to have a trap and an Email sent whenever the currently indexed variable on the currently
indexed device enters the Breach of Warning High Limit state, you should set
ssTrapOnScalarWarningEnable and ssEmailOnScalarWarningEnable to 1.
Setting Breach Limit on Boolean Variables
The reading of the currently indexed Boolean variable on the currently indexed device is given by the
ssBooleanData MIB object.
A Boolean variable will enter alert state when its reading is equal to the user defined Boolean critical value.
The Boolean critical value is set through the ssBooleanCriticalState MIB object, and can be assigned one
of the two possible Boolean values. The two possible Boolean values are stored in the MIB objects
ssBooleanZeroStateString and ssBooleanOneStateString. For example, to be alerted when your power
sensor detects power failure, set ssBooleanCriticalState to “PWR FAIL”.
There are two possible alert states for each Boolean variable:
Breach Of Boolean Critical Limit
Return to Normal
Different alert actions can be taken in each alert state. The following alert actions are supported:
Email
SMS-Paging (SSA7004 and SSA7008 only)
SNMP Traps
Command line execution
Any combination of these alert actions can be taken when the variable enters a particular alert state. Please
note that SMS-Paging cannot be configured through SNMP. Please use the Alert web interface to
configure any SMS-Paging alerts.
51