Cut Sheet

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/sensorswitch
© 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/04/22
WSXA SERIES
4 of 4
LOAD
PNK
PNK
*
GRY
0-10V Dimming Common may be pink or as otherwise
indicated per section 410.69 of the 2020 NEC
*
PNK
LOAD
PNK
PNK
*
GRY
0-10V Dimming Common may be pink or as otherwise
indicated per section 410.69 of the 2020 NEC
*
PNK
WSX Family (IS-WSXA-003)
Notes:
All load controls act in unison
Black wires can be used interchangeably
Violet and pink wires are not present on devices
without D option
Cap off violet and pink wires if dimming
functionality is not being used
Red Wire is not present on devices without MWO
option
Cap off red wire if Multi-Way functionality is not
being used
For ground Multi-Way Congurations ground must
come from same source
For neutral conversion Multi-Way Congurations
power must come from the same panel
Per NEC requirements, the 0-10V violet and pink
wires must be installed as Class One.
SPODMRA MWO paired with WSXA MWO will act
accordingly with WSXA occupancy settings
The 0-10V control wires must not exceed 250 ft
(76 m) in length and must be sized at no less than
20 AWG
The Low Voltage Communication BUS must not
exceed 250 ft (76 m) in length and must be sized
at no less than 20 AWG
Dimming wires from individual MWO devices
should only connect with xture/driver dimming
wires and never to another MWO device
CONVERTIBLE NEUTRAL GROUND ONLY
SINGLE RELAY, 120-277 VAC SINGLE RELAY, 120-277 VAC
SINGLE RELAY, 347 VAC SINGLE RELAY, 347 VAC
SINGLE RELAY, MULTI-WAY CONFIGURATION, 120-277 VAC SINGLE RELAY, MULTI-WAY CONFIGURATION, 120-277 VAC
WIRE COLOR KEY
120-277 VAC WIRING
BLK - Line Input
BLK - Line Output
VIO - Low Voltage Dim Output (0-10 VDC)
PNK - Low Voltage Common
RED - Low Voltage Communication Wire
347 VAC WIRING (-347 Option)
Orange (ORN) wires replace black (BLK) wires
***Some Pink wires may come as Gray
WIRING
PNK
*
0-10V Dimming Common from
fixture may be pink or as
otherwise indicated per section
410.69 of the 2020 NEC
GRY PNK
*
PNK
*
0-10V Dimming Common from
fixture may be pink or as otherwise
indicated per section 410.69 of the
2020 NEC
GRY PNK
*
PNK
*0-10V Dimming Common from
fixture may be pink or as otherwise
indicated per section 410.69 of the
2020 NEC
GRY PNK
*
PNK
*0-10V Dimming Common from
fixture may be pink or as otherwise
indicated per section 410.69 of the
2020 NEC
GRY PNK
*
NH
WSX (PDT) 2P
BLU
BLK
BLK
GRN
IF REQUIRED
120V/277V
BLU
LOAD A
LOAD B
WHT
* 0-10V Dimming Common from fixture
may be pink or as otherwise indicated
per section 410.69 of the 2020 NEC
2 POLE CONFIGURATION