Cut Sheet

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/sensorswitch
© 2014-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/04/22
WSXA SERIES
3 of 4
Electrical Input Ratings 120-277VAC, 50/60 Hz
347VAC, 50/60 Hz (with 347 option)
Output Ratings 120VAC, 800W, 6.7A - Tungsten, Standard Ballast, Electronic Ballast
277VAC, 1200W, 4.3A - Tungsten, Standard Ballast, Electronic Ballast
347VAC, 1500W, 4.3A - Tungsten, Standard Ballast, Electronic Ballast
120/277/347VAC, 1/4 HP - Motor
Relay Type Latching
Low Voltage Output Ratings 0-10VDC, Sinks <50mA
Standards/ Ratings Energy Management Equipment, UL916 (E167435)
Mechanical Dimensions 2.74”H x 1.68”W x 1.63”D (70mm x 43mm x 41mm) - does not include ground strap
Mounting Single-Gang Box
Connection Type Low-Voltage Leads, Line-Voltage Leads
Environmental Warrantied Operating Temperature 32°F to 140°F (0°C to 60°C)
Relative Humidity Up to 90%, Non-Condensing
Standards/ Ratings RoHS
SPECIFICATIONS
COVERAGE PATTERNS
36 30 20 10 0 ft 10 20
30 36
12 9 6 3 0 m
3 6 9 12
Small
motion
detection
Small
motion
detection
to ~20 ft
6
3
0 m
20
10
0 ft
Small motion ~40 ft coverage
TOP VIEW
1.2 m
4 ft
Small motion
detection to ~20 ft
Large motion detection to >36 ft
SIDE VIEW
0 18 27 369
ft
0 6 9 123
m
Small motion (e.g. hand movements)
detection up to 20 ft (6.10 m), ~625 ft2
Large motion (e.g. walking) detection greater
than 36 ft (10.97 m), ~2025 ft2
Wall-to-wall PIR coverage
Units with -PDT (Passive Dual Technology)
option (also called Microphonics) provide
overlapping detection of human activity over
the complete PIR coverage area. Advanced
ltering is utilized to prevent non-occupant
noises from keeping the lights on.
Tested to NEMA WD 7-2011
Step 1:
Remove Yellow
Label
Step 2:
Loosen Screws and
Remove Metal Link
Step 3:
Connect Neutral to
Silver Screw and
Ground to Green
Screw
CONVERSION FROM GROUND ONLY NO NEUTRAL TO NEUTRAL WIRING
This product is pre-configured for wiring without a neutral; however, if connection to neutral is required by code, the unit easily converts in seconds.