WIRING (DO NOT WIRE WHEN ENERGIZED)
WIRING TO SINGLE PHASE POWER (120/277/347 VAC)
BLACK - 120/277/347 VAC Input
BLUE - Switched Line Voltage Output to Luminaire
WHITE - Neutral
VIOLET - Low Voltage Dim Output (0-10 VDC)
PINK - Low Voltage Common (0-10 VDC)
UL924 Sequence of Operation (EM Option):
For 90 minutes following any complete AC power interruption >30 ms:
• Relay is closed and 0-10V dimming is at high end trim level
• Device ignores wireless lighting control commands
• If another nLight AIR device in the nLight AIR group (as dened by CLAIRITY+) is on normal power, and has its power restored prior to the 90-minute timeout, the “EM” device will exit this
override state and return to normal operation. This is accomplished by having a normal power device send an “exit EM” message to the “EM” device
• Devices that will send the “exit EM” command when normal power is present
• Dimming Power Pack Devices (rPP20 D/DS)
• ER Non-Dimming and Dimming Power Pack Devices (rPP20 D/DS ER)
• Other nLight AIR Non-“EM” Devices (rLSXR, rSBOR, rSDGR, rIO, rES7, rMSOD)
• Devices that will not send the “exit EM” command when normal power is present
• Non-Dimming Power Pack Devices (rPP20)
• Other nLight AIR “EM” Devices (rPP20 EM, rLSXR EM, rSBOR EM, rSDGR EM, rIO EM, rES7 EM, rMSOD EM)
• Ceiling Mount Sensors (rCMS)
• Wall Switches (rPODB, rPODL)
• nLight Air Adapter (nECYD)
• Upon power up, “EM” devices will be at high trim setting for 90 minutes. During commissioning with CLAIRITY+, the device will exit this override when a device is identied or added to the
grid.
WIRING TO 2-PHASE POWER* (208/240/480 VAC)
BLACK - 208/240/480 VAC Phase A Input
BLUE - Switched Line Voltage Output to Luminaire
WHITE - Phase B of 208/240/480 VAC Input
VIOLET - Low Voltage Dim Output (0-10 VDC)
PINK - Low Voltage Common (0-10 VDC)
*Safety Note: only one line phase is being switched
Factory install required
WIRING TO EMERGENCY (-EM) UNITS
BLACK - 120/277 VAC Input Emergency Hot
BLUE - Switched Line Voltage Output to Luminaire
WHITE - Emergency Neutral
VIOLET - Low Voltage Dim Output (0-10 VDC)
PINK - Low Voltage Common (0-10 VDC)
EMERGENCY
LUMINAIRE BALLAST
or
LED DRIVER
Emergency
PNK PNK
*
GRYPNK
*
GRY
0-10V Dimming Common may be pink or as otherwise
indicated per section 410.69 of the 2020 NEC
*
LUMINAIRE
BALLAST
or
LED DRIVER
0-10V Dimming Common may be pink or as otherwise
indicated per section 410.69 of the 2020 NEC
*
PNK PNK
*
GRYPNK
*
GRY
LUMINAIRE
BALLAST
or
LED DRIVER
PNK PNK
*
GRYPNK
*
GRY
0-10V Dimming Common may be pink or as otherwise
indicated per section 410.69 of the 2020 NEC
*