Cut Sheet

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com
© 2014-2016 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/16/16
NSP5-PCD TN-611
2 of 2
GROUND
GROUND
N
nSP5 PCD 3W
CAT-5
3 WIRE
DIMMABLE
BALLAST
BLK
RED
WHT
BLU
H
N
nSP5 PCD 2W
nSP5 PCD MLV
nSP5 PCD ELV 120
CAT-5
BLK
RED
WHT
H
2 WIRE
BALLAST or
MLV/ELV LOAD
(SWITCHED HOT)
(DIMMED HOT)
GROUND
GROUND
N
nSP5 PCD 3W
CAT-5
3 WIRE
DIMMABLE
BALLAST
BLK
RED
WHT
BLU
H
N
nSP5 PCD 2W
nSP5 PCD MLV
nSP5 PCD ELV 120
CAT-5
BLK
RED
WHT
H
2 WIRE
BALLAST or
MLV/ELV LOAD
(SWITCHED HOT)
(DIMMED HOT)
WIRING (DO NOT WIRE HOT)
Device power is provided via the CAT-5e connection and not taken off the line. T568B pin/pair assignment is recommended for all CAT-5e cables. For dimming
120 VAC incandescent loads use the 2-wire diagram below. In multi-phase applications, use a separate neutral for each phase containing a dimmer circuit.
Additional notes on usage of nSP5 PCD ELV 120 module:
1. Caution: module should not be used to dim a load fed from a local step-down transformer.
2. Caution: to avoid overheating and possible damage to other equipment, do not use module to control receptacles, magnetic uorescent lighting xtures,
motor-operated, or transformer-supplied appliances.
3. Use only to control the primary side of electronic transformer-supplied low-voltage lighting.
4. Some xture manufacturers do not recommend dimming their solid-state transformers. To determine if a xture may be dimmed, consult literature of the
xture manufacture.
Several operational settings for the nSP5 PCD are available:
Override (On/Off/Normal)
Occupancy Tracking (Enable/Disable)
Photocell Tracking (Enable/Disable)
Switch Tracking (Enable/Disable)
Local Occupancy Tracking Channel (1-16)
Local Photocell Tracking Channel (1-16)
Local Switch Tracking Channel (1-16)
Global Tracking (Enable/Disable)
Global Tracking Channel (1-128)
Button Mode (Enable/Disable)
Invert Relay Logic* (Enable/Disable)
*does not invert dimming operation
Idle Time Until Dim
Dimming Range High (0 - 100%)
Dimming Range Low (0 - 100%)
Dimming Offset (-200% to +200%)
LED (Override On/Override Off/Normal)
Follow Photocell Mode (Enabled +, Enabled +/-, Disabled )
WallPod Dimming Adjustments (Perm., Temp., Photocell Temp. Override)
Special Modes:
Manual On to Auto Off (Semi-Auto), Auto to (Timed) Override On
Manual to (Timed) Override On, Manual On to Full Auto, Predictive Off
Frequency (60 Hz / 50 Hz)
OPERATIONAL SETTINGS
SPECIFICATIONS
Size: (not including 1/2” chase nipple)
3.38” H x 2.53” W x 1.83” D
(8.59 cm x 6.43 cm x 6.22 cm)
Weight: 6 oz
Mounting: 1/2” knockout (open air only)
Network Connection: 2 RJ-45 ports
Bus Power Consumption: < 7 mA
Switching/ Dimming Ratings nSP5 PCD 2W
575 W @ 120 VAC, 1375 W @ 277 VAC,
Tungsten / Ballast
nSP5 PCD 3W
575 W @ 120 VAC, 1375 W @ 277 VAC, Ballast
nSP5 PCD MLV
575 W @ 120 VAC, 1375 W @ 277 VAC
(MLV Transformers only)
nSP5 PCD ELV 120
475 W @ 120 VAC
Minimum Load: nSP5 PCD 2W/3W/MLV: 7W
nSP5 PCD ELV 120: None
Default Trim Levels: 2W/3W
56 to 110 VAC w/ 120 VAC feed
129 to 254 VAC w/ 277 VAC feed
MLV/ ELV
24 to 117 VAC w/ 120 VAC feed
55 to 270 VAC w/ 277 VAC feed
Wires: nSP5 PCD 2W/MLV/ELV 120: 18 AWG (4)
nSP5 PCD 3W: 18 AWG (5)
Title 24 System Component, ROHS Compliant