Cut Sheet

Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight
© 2019-2022 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/14/22
nPODMA
4 of 4
Electrical Input Ratings 15-24VDC, 5mA, Class 2 (nLight network power)
Standards/Ratings Energy Management Equipment, UL916 (E167435)
Mechanical Dimensions 2.74”H x 1.68”W x 1.63”D (70mm x 43mm x 41mm) - does not include ground strap
Mounting Single-Gang Box or Low Voltage Ring
Connection Type RJ-45 nLight Network Ports (2)
Environmental Warrantied Operating Temperature 32°F to 140°F (0°C to 60°C)
LT Option: -4°F to 140°F (-20°C to 60°C)
Relative Humidity Up to 90%, Non-Condensing
Standards/ Ratings RoHS
Security Complies with California Civil Code Title 1.81.26, Security of Connected Devices,
approved under Senate Bill No. 327 (2018)
SPECIFICATIONS
Ensure CAT-5e cable(s) an effectively fed through the gang box
Push the CAT5e cables through the back of the gang box
Remove the wall plate from the device by pulling the sides out to expand the wall plate and
release it from the mounting anges.
Access RJ-45 port(s) on the WallPod by sliding the plastic guard up
Insert the CAT-5e cable(s) to the RJ-45 port(s)
Slide the guard back onto metal strap
Connect the unit to the gang box
The unit will connect to the gang box by screws, one at the top and one at the bottom
To ensure correct wall plate installation, drive the screws until the mounting anges
contact the wall surface. If the screws are overdriven, the mounting anges will disengage,
preventing wall plate installation. If this happens, reattach the mounting ange(s) and
install to correct position. (The anges may be reattached by inserting the two tabs in the
side of the unit and pushing the part inward to engage the three snaps.)
Reattach the wall plate
Expand the wall plate horizontally
Place the wall plate onto the unit
Contract the horizontally expanded wall plate onto the unit such that the side ange
features seat inside the wall plate
SLIDE
TO RJ-45 PORT
TO RJ-45 PORT
PROGRAMMING
Refer to instruction card IN-11.3 for directions on programming the switch via the upper-most left push-button. All buttons are factory set to the matching switch channel
(button 1 - channel 1, button 2 - channel 2, etc). For nPODMA 4P DX, channels to be controlled are selected rst, then the control button (on/off or raise/lower).
For 2L and 4L variants, the preset dim level of a button can be changed by rst adjusting the light level with either the units raise/lower buttons (nPODM 4L DX) or via
another raise/lower WallPod broadcasting on the same switch channel (necessary with a nPODM 2L). Once lights are at desired level, hold a LEVEL button for 8 seconds
until the LED ashes. Levels can also be set via SensorView.
INSTALLATION
Attention! Only use non-booted CAT5e cables.