Cut Sheet
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com/nLight
© 2014-2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 01/02/19
nCM xx RJB - TN-139-001
3 of 4
Wiring an nCM xx ADCX RJB to an nLight Dimming Pack
Wiring to an nLight Enabled Luminaire
Wiring to an nLight Relay Pack
TYPICAL APPLICATIONS
The following instructions are for mounting sensor directly to a ceiling tile or sheetrock
surface. Sensor’s mounting holes also align with standard round fixture or single gang
handy box (screws not provided).
1. Using template included with unit, mark spots on ceiling tile/sheetrock for cable hole
and mounting anchors/screws
2. Drill 1/2” hole through ceiling surface at location indicated on template
3. Insert provided anchors into ceiling surface at locations indicated on template
4. Remove provided RJ-45 splitter from sensor’s attached CAT5e cable and then thread
cable (and low voltage wires if -AR option included) through hole from underside
5. Mount sensor to anchors using two screws provided
6. Attach provided RJ45 splitter device (model CAT5 Y) above ceiling to cable from sensor
(see diagram on right)
7. Interconnect CAT-5e cables to/from rest of nLight zone to RJ45 splitter
8. Once power is received via CAT-5e connection, all devices in zone will automatically
begin functioning together according to each device’s defaults
9. Install decorative sensor lid by rotating clockwise
10. Refer to included instruction card for default settings and directions on push-button
programming.
CAT-5e
BRN
BRN
CAT-5e Splitter
CAT-5e
CAT-5e
- AR option
(contact closure)
to/from nLight
Zone
TYPICAL APPLICATIONS
nPP16
WHT
(neutral)
BLU
(line in)
BLU
(line out)
CAT-5e
120 VAC
OR
277 VAC
1
BLK
1
(line in)
ORN
1
(line in)
LOAD
To other nLight
devices (optional)
CAT-5e
CAT-5e Splitter
(included)
CAT-5e
CAT-5e
To other nLight
devices (optional)
nCM xx RJB
WHT(neutral)
BLU (line in)
BLU (line out)
VIO (low voltage dim out)
GRY (low voltage common)
GRN
CAT-5e
nPP16 D
or
nPP16 DS
0-10 VDC
Ballast or
LED Driver
120 VAC
OR
277 VAC
1
ORN
1
(line in)
BLK
1
(line in)
To other nLight
devices (optional)
CAT-5e Splitter
(included)
CAT-5e
CAT-5e
To other nLight
devices (optional)
nCM xx ADCX RJB
CAT-5e
To other nLight
devices (optional)
nLight Enabled
Luminaire
CAT-5e Splitter
(included)
CAT-5e
CAT-5e
To other nLight
devices (optional)
nCM xx RJB
or
nCM xx ADCX RJB