INSTALLATION
WIRING (DO NOT WIRE HOT)
COVERAGE PATTERN
0 ft
9
0 m
2.7
28 21 14 7 0 ft 7 14 21 28
8.5 6.4 4.3 2.1 0 m 2.1 4.3 6.4 8.5
SIDE VIEW
TOP VIEW
28
14
0 ft
14
28
8.5
4.3
0 m
4.3
8.5
0 ft
9
0 m
2.7
28 21 14 7 0 ft 7 14 21 28
8.5 6.4 4.3 2.1 0 m 2.1 4.3 6.4 8.5
SIDE VIEW
TOP VIEW
28
14
0 ft
14
28
8.5
4.3
0 m
4.3
8.5
Best choice for large motion (e.g. walking) detection
Viewing angle of 67º in a 360º conical shaped pattern
Provides 28 ft (8.53 m) radial coverage when mounted to standard 9 ft
(2.74 m) ceiling
7 to 15 ft (2.13 to 4.57 m) mounting heights provide 16 to 36 ft (4.88 to
10.97 m) radial coverage
Microphonics™ provides overlapping detection of human activity over
the complete PIR coverage area. Advanced ltering is also utilized to
prevent non-occupant noises from keeping the lights on.
10 EXTENDED RANGE 360º LENS WITH MICROPHONICS
[R] Relay Option
[D, P, ADC] Photocell / Dimming Options
POWER PACK
(PP20)
RED
WHT
BLK
VIO w/ WHT STRIPE (+)
(-)
Mount sensor directly to a ceiling tile or a metallic grid (two
self-tapping screws provided).
Sensor’s mounting holes also align with 3.5” octagon or
single gang handy box (screws not provided).
Sensor will detect motions crossing segments more
effectively than motions parallel to beams.
For optimal detection, position sensor such that segments
are crossed upon entrance and unable to view outside the
space.
PUSH BUTTON
PROGRAMMING
Refer to instruction card IC7.002 for default settings and directions on programming the sensor via the push-button.
Note:Sensor’s
screw axis is offset
7.5º from a long
detection segment
*At 9ft Mtg.
A: When walking across beam, detection
will occur at approximately 28 ft (8.53 m)
B: When walking into beam, detection will
occur at approximately 24 ft (7. 32 m)
STANDARD WIRING
RED - Power Input (12-24 VAC/VDC)
BLACK - Common
WHITE - Occupancy State (high VDC for occupied)
RELAY OPTION (R)
GRAY / BROWN - Connected during occupied state
VIOLET / BROWN - Connected during unoccupied state
Note: Relay is energized during unoccupied state
PHOTOCELL/DIMMING OPTIONS (D, P, ADC)
BLUE - Direct output to power pack for providing photocell
control and/or secondary dim time out. Output is high VDC
with occupancy & low light. Output also held high during
secondary dim time out. For multi-level control, use two
power packs and connect White wire to primary load and
Blue to daylight load.
VIOLET w/ WHITE STRIPE - Connect to 0-10 VDC control
wire (typically Violet) from 0-10 VDC dimmable ballast
GRAY from Ballast - Connect to sensor Black wire