Installation Manual
2  OCCUPANCY TIME DELAY
  The  length  of  time  an  occupancy  sensor  will  keep  the  lights 
on  and  at  full  bright  after  it  last  detects  occupancy  (assuming 
minimum on time has been met)
3  DIM TO OFF TIME 
  An extended length of time after the occupancy time delay has 
expired that a sensor will rst reduce lighting to the low dimming 
range setting before turning completely off
4  100 HOUR BURN-IN / AUTO SET-POINT
  Test Mode 
  Disables Minimum  On Time, sets Occupancy Time Delay to 
30  sec,  and  shortens  all  photocell  transition  and  dimming 
rates. Mode will expire after 10 min or if function 4 is set back 
to Normal.
  100 HOUR BURN-IN 
  Overrides  relay  on  and/or  dimming  output  to  full  bright 
(typically for lamp seasoning)
  AUTO SET-POINT
  Photocell calibration procedure for detecting optimum lighting 
control level
5  TEN’S DIGIT OF SET-POINT
  The ten’s digit of the target light level that is to be maintained by 
the device (in foot-candles)
6  ONE’S DIGIT OF SET-POINT
  The one’s digit of the target light level that is to be maintained by 
the device (in foot-candles)
7  SUNLIGHT DISCOUNT FACTOR
  Value used to improve the tracking accuracy of a photocell during 
periods  of  high  daylight.  Decreasing  the  value  will  lower  the 
controlled level of the lights
8  INCREMENTAL SET-POINT ADJUSTMENT
  Alters the target light level that is to be maintained by the device 
(in foot-candles)
10 MINIMUM ON TIME
  The length of time required for lamps to be on in order to prevent 
all short cycling that shortens lamp life. If occupancy time delay 
expires prior to minimum on time being satised, the lamps will 
remain on until time has been met.
11  PHOTOCELL MODE
  Indicates  a  photocell  sensor’s method  of  operation.  One  mode 
enables the  sensor  to turn the  lights both on  and off, while the 
other mode can only inhibit the lights from turning on. For dimming 
sensors, this mode enables disabling of on/off functionality.
12 DUAL TECHNOLOGY (MICROPHONICS
TM
)
  A second method of occupancy detection that allows the sensor 
to hear occupants
14 LAMP INFORMATION
LAMPMAXIMIXER+ (Enable/Disable)
Advanced  operating  mode  where  occupancy  time  delay 
adjustments  are  automatically  made  every  two  weeks. 
The  time  delay  is  adjusted  according  to  an  algorithm  that 
determines the optimum time delay in order to maximize both 
lamp life and energy savings.
TOTAL SWITCHES
The current count (in 1000’s) of the number of off to on cycles 
since sensor installation (or since count was manually reset)
TOTAL RUN-TIME
The current elapsed time (in 1000’s of hrs) a controlled lamp 
has been on since sensor was installed (or since count was 
manually reset)
RESET LAMPMAXIMIZER+
Method  of  clearing  the  sensor’s  historical  occupancy 
information such that if a sensor is phycially moved, only new 
occupancy information will inuence LampMaximizer+ results
15 DIMMING RANGE (HIGH) 
  The  maximum  output  level  (0-10  VDC)  of  a  sensor  with  a 
dimming output
16 DIMMING RANGE (LOW) 
  The minimum output level (0-10 VDC) of a sensor with a dimming 
output
FUNCTION DEFINITIONS
NOTE: 
For  information  on  additional  advanced  settings,  including 
resetting unit to factory defaults, contact:
Technical Support: 1.800.727.7483
DOC# IC7.001
Date Code 2410
1.800.PASSIVE
OCCUPANCY SENSOR 
PROGRAMMING INSTRUCTIONS