Cut Sheet
900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a 
period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material 
Authorization number and repair or replace returned product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied 
warranties  (including  the implied warranties of merchantability and  tness  for  use)  and  under  no  circumstances  shall 
Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
TS-CMR-003A
Revised 10.29.2010 © 2010 Sensor Switch 
INSTALLATION
WIRING (DO NOT WIRE HOT)
COVERAGE PATTERN
30 20 10 0 ft 10 20 30
9.1 6 3 0 m 3 6 9.1
0 ft
15
30
45
0 m
4.6
9.1
13.7
LOW VIEW
HIGH VIEW
0 ft
15
0 m
4.6
 20 10 0 ft 10   20
 6 3 0 m 3 6
6 HIGH BAY 360º LENS
•  Best choice for 15 to 45 ft (4.57 to 13.72 m) mounting heights
•  15 to 20 ft (4.57 to 6.10 m) radial coverage overlaps area lit by a typical 
high bay xture
•  Excellent detection of large motion (e.g. walking) up to a 35 ft (10.76 
m) mounting height
•  Excellent detection  of extra large  motion  (e.g. forklifts) up  to  a 45 ft 
(13.72 m) mounting height
PROGRAMMING
Refer to instruction card IC7.001 for default settings and directions on programming the sensor via the push-button.
STANDARD WIRING
  BLACK*  - Line Input
  BLACK*  - Load Output
  WHITE  - Neutral
347 VAC OPTION (347)
  Black wires are replaced w/ Red wires
INITIAL POWER UP
 The sensor’s relay is shipped in a latched closed position so the lights 
will come on upon initial power-up. If the lights do not immediately turn 
on (initial installation only) the latching relay opened during shipment 
and will close within 30 secs.
Note: If the sensor loses power, the internal relay will latch to on.
DIMMING OPTION (D)
VIOLET - Connect to Violet control wire from 
  0-10 VDC dimmable ballast
GRAY - Connect to Gray common wire from 
  ballast
*BLACK wires can be reversed
} 
BLK
BLK
VIO (+)
WHT
GRY (-)
[D] Dimming Option
H
N
SWITCH
LOAD
PUSH BUTTON
•  Sensor’s mounting holes align with a standard 3.5” octagon box or a 
single gang handy box (screws not provided).
•  Heat producing sources controlled by the sensor must not be in the 
view pattern of the sensor. If sensor cycles or appears to continually 
stay on, move sensor or mask lens segments that view the source.
•  A label kit is included to mask off half of the sensor’s coverage pattern 
for end of aisle, or trim the side viewing to create a rectangular pattern 
for center of aisle.
CENTER OF AISLE
END OF AISLE