Specifications

3
I. SPECIFICATIONS
Model:
SEC MILLENIUM Infrared Carbon Dioxide (CO2) Gas Detector
Part Number: 142-0617
Specify range when ordering
Detection Method:
Diffusion
Optional sample draw (requires a minimum of 1 liter per minute flow rate)
Available Ranges:
0-1% Volume
0-2% Volume
0-5% Volume
(1 % volume = 10,000 PPM)
High level CO2 (and hydrocarbon gases) monitors available in SEC Signature product line
Output (analog):
4-20 mA (Source type), max. 1000 Ohm load at 24 VDC supply voltage
Response Time:
T50 < 5 seconds
T90 < 10 seconds
Construction:
Sensor housing is nickel-plated aluminum and stainless steel.
Optional stainless steel model available.
Class 1, Division 1, Groups B, C and D
Ingress rating: IP54
Accuracy:
+/- 5% measured value or +/- 3% full scale (whichever greater)
Operating Temperature Rating:
-40° to +70°C at 0 to 99% RH (non-condensing)
Operating Voltage:
24 VDC Operating range: 18 to 32 VDC measured at the detector head
Power Consumption: 5 Watts Max.
Current Draw: (at 24 VDC)
Average: 250 mA
Peak: 400 mA
Approvals: CSA and FM, For -40C to +50C operation
Installation Category: Cat. I, Pollution Degree 2