The ISOSLICE-9 unit has 4 ac analog inputs.
Default input types and ranges
Default input ranges are 0 to 1A AC. The ISOSLICE-9 is used with a range of current
transformers which produce output in this range, but with variable input range in ac Amps.
Channel number
The channel number is selected using S4. The channel number must be between 2 and
128, using switches 2 to 8. If all switches are off, the channel number is 1 (invalid):
The channel number is a binary reading of switches 2 to 8, with switch 8 the lowest bit.
S4 1 = On, 0 = Off
Channel 2 3 4 5 6 7 8 Channel 2 3 4 5 6 7 8
1 0 0 0 0 0 0 0 9 0 0 0 1 0 0 0
2 0 0 0 0 0 0 1 10 0 0 0 1 0 0 1
3 0 0 0 0 0 1 0 11 0 0 0 1 0 1 0
4 0 0 0 0 0 1 1 12 0 0 0 1 0 1 1
5 0 0 0 0 1 0 0 13 0 0 0 1 1 0 0
6 0 0 0 0 1 0 1 14 0 0 0 1 1 0 1
7 0 0 0 0 1 1 0 15 0 0 0 1 1 1 0
8 0 0 0 0 1 1 1 16 0 0 0 1 1 1 1
S4
S4 selects the isoslice bus channel (2 to 128)