Battery type AGM GEL Wet
Bulk charge phase
Bulk
Bulk charge current limit SEE SPEC (PAGE 5)
Bulk phase terminates
1. When battery voltage reaches the Acceptance voltage
2. When the bulk timeout is reached
Bulk phase timeout
6 hours 6 hours 6 hours
Bulk timers will extend when load management reduces charger
current below 50% (25A)
Acceptance charge phase
Acce
p
tance
Acceptance charge
voltage @ 77F/25C
14.3 VDC 13.7 VDC 14.6 VDC
Acceptance voltage
temp comp
5mv/cell/°C
Maximum acceptance
voltage at low temps
15.0 VDC @ 4C 14.5 VDC @ -6C 15.0 VDC @ 10C
Acceptance phase
terminates
1. When charge current is reduced
2. When the acceptance timeout is reached
3. If the charger can’t maintain the Acceptance voltage
Acceptance phase
timeout
6 hours
Float charge phase
Float
Float voltage @
77F/25C
13.4 VDC 13.4 VDC 13.2 VDC
Float voltage temp comp 5mv/cell/°C
Battery Temperature
Batter
y
Tem
p
Charger Warm Battery:
output switches to
compensated float from
Bulk/Accept/Off(hot)
>122F/50C
<140F/60C
Charger High Battery
Temp: Output to Off
>140F/60C
Charger Resumes in
previous mode:
Bulk/Accept/Float
<112F/45C