Connect the lug end of the temperature compensation cable to the negative post of
the most negative point in the battery bank. Connect the two pin connector to the
appropriate mating connector located at the side of the inverter labeled “Temp.
Sense.” Use the slide switch on the right side of the inverter and select the battery
type that you are using for proper battery charging.
NOTE: If the temp. Comp. Cable or Dongle is not connected; the battery charger
will not function
WARNING: Do not connect another source of
AC power directly to the output of the inverter. This
will result in damage not covered under warranty.
The inverter’s 120 VAC output power is provided at
the GFCI receptacle and the hard wire terminal
blocks behind the access panel.
Wire the AC Input to the hard wire terminal blocks
behind the access panel for charging and shore power.
NOTE: Remove the black hole covers as needed for
hardwire AC wiring. Use a romex type clamp to
protect the wires from the metal edge of the hole.
Apply 14.6 in/Lbs torque to the terminal block
screws.
NOTE: Systems rated at 2500 watts and above should be powered with a 30A
circuit.
NOTE: Connecting the plug-in cord to GFCI protected outlets may cause some
interference with the inverter’s GFCI.
NOTE: For GFCI protected hardwire output. Wire directly to the GFCI “Load”
terminals. Verify that you are connecting to the un-used “Load” terminals.
TEMP COMP CABLE CONNECTION
AC INPUT & OUTPUT CONNECTIONS
Tighten to 14.6 in/Lbs