1) No AC output power during inverter mode:
Check the in-line fuse which is located within 18” from the battery’s
positive post.
DC connections tight and clean?
Is output circuit breaker tripped?
Check the inverter power switch and remote power switches.
Check the GFCI to see if it is tripped, and reset if necessary.
- If GFCI is set, disconnect all loads and connect a test light.
- If the test light is off, replace GFCI or return the inverter for service.
For model 12LP10H, check AC hardwire connections.
Note: If the status LED's are illuminated, refer to the “LED Status Chart” on the
previous page for additional information.
2)
Low Battery: The use of a battery isolator is not recommended due to
excessive voltage drop across isolator terminals.
Battery voltage must be above 10.5/11.7 VDC ) (measured at the inverter)
for the inverter to be on.
Check for proper DC wire gauge (see DC Wire Gauge & Fusing section)
3)
Overload: Unplug all loads and reset the inverter On/Off.
If the overload condition clears, check for short circuits or check load size
versus inverter output wattage size.
If the overload persists, possible failed inverter
4)
High Temperature: Let the inverter cool down
Troubleshooting
14
Verify that all vent openings are clear of obstruction.
Reduce ambient temperature and/or load.