Usage: Any 120 VAC, 60 Hz single phase prod
uct wit
hin the inve
r
ter’s power rating.
The inverter front “STATUS LED will be Green while the inverter is on. The
AC power produced by the inverter comes from the energy stored in the
battery bank through a sophisticated electronic inversion process. A
transformer, a Metal Oxide Silicon Field Effe
ct Transistors (MOSFET), a filter
capacitor and microprocessor control are used to generate clean AC power.
The inverter will operate at DC input voltages ranging from 10.5 to 16 volts.
Above 16 volts the inverter may stop operating due to input voltage being out of
range. The inverter can tolerate up to 24V DC for 5 minutes. Durations longer
than 5 minutes will result in a shut down. Input voltages above 24V DC will result
in an immediate shutdown. The inverter will restart when the input voltage drops
below 16V DC. When the input voltage drops to 10.5/11.7 volts, the inverter will
stop operating due to a low battery condition. When the lead acid battery bank
voltage drops to 10.5 volts, the battery is fully discharged.
Note: The signal output waveform produced by the inverter when in
inverter mode” is pure sinusoidal. It has a total harmonic distortion of less
than 5% at nominal input.
Refer to the “LED STATUS CHART” below for LED descriptions.
WARNING: Do not remove chassis cover. No user-serviceable parts
inside. Call or e-mail customer service for free consultation during business hours
(7:30am-5:30pm central time) at 1-800-553-6418 or 1-651-653-7000; fax 1-888-439-3565 or
1-651-653-7600 E-mail: inverterinfo@sensata.com; Website: http://dimensions.sensata.com
Mode Inverter LED
(Bi-color)
Remote Switch LED
(Red)
ON (normal operation
or sleep mode
)
Green, constant Constant
Low battery 0-5 sec Orange, constant 0-5 sec Constant
Overload 0-5 sec Red, constant 0-5 sec Constant
Low battery > 5 sec Red, 1 blink 1 blink
Overload > 5 sec Red, 2 blinks 2 blinks
High temperature Red, 3 blinks 3 blinks
Feedback fault Red, 4 blinks 4 blinks
High battery 0-5 mins Red, 5 blinks
Constant
High battery > 5 minutes
or > 24V
Red, 6 blinks
6 blinks
THEORY OF OPERATION
Inverter Power Mode
LED Status Chart
13
TROUBLESHOOTING GUIDE
Off (Inv. Switch Off or
Shutdown B
y Timer)
Off
Off