SPECIFICATIONS
Output
(2)
Description 25A 30A 50A 55A 60A 75A
Operating Voltage (47-440Hz) [V
RMS
]
48-600 48-600 48-600 48-600 48-600 48-600
Transient Overvoltage [Vpk]
(3)
1200 1200 1200 1200 1200 1200
Maximum Off-State Leakage Current @ Rated Voltage
[mA
RMS
]
1 1 1 1 1 1
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/
μsec]
500 500 500 500 500 500
Load Current, General Use UL508/LC A IEC62314 @ 40°C
[A
RMS
]
25 30 50 55 60 75
Load Current, Motor Starting UL508 FLA/LC B IEC62314 @
40°C [A
RMS
]
6.4/3.9 6.4/3.9 12/6.8 12/6.8 21/17.6 21/17.6
Minimum Load Current [mA
RMS
]
100 100 100 100 150 150
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
286/300 286/300 716/750 716/750 1290/1350 1290/1350
Maximum On-State Voltage Drop @ Rated Current [V
RMS
]
1.25 1.3 1.25 1.3 1.15 1.20
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec]
409/375 409/375 2563/2343 2563/2343 8320/7593 8320/7593
Minimum Power Factor (at Maximum Load)
0.5 0.5 0.5 0.5 0.5 0.5
Motor Rating UL 508: 120 VAC / 240 VAC / 480 VAC [HP]
0.5/1.0/3.0 0.75/1.0/3.0 1.5/3.0/7.5 1.5/3.0/7.5 3.0/5.0/15.0 3.0/5.0/15.0
Motor Rating IEC62314: 240 VAC / 400 VAC / 500 VAC [kW]
0.75/1.5/2.2 0.75/1.5/2.2 1.5/3.0/4.0 1.5/3.0/4.0 4.0/7.5/11.0 4.0/7.5/11.0
ORDERING OPTIONS
Example : PM6760A25RPTA
Description of part number example
Operating Voltage
Control Voltage
Family
Rated Load Current
Switching Type
Overvoltage Protection
Over Temperature Protection
(1)
D = 4-32 VDC (4-28 VDC for TA option)
A = 90-280 VAC/VDC
PM67 60 x xx x P
xx
25 = 25A, 3-legs
30 = 30A, 2-legs
50 = 50A, 3-legs
55 = 55A, 2-legs
60 = 60A, 3-legs
75 = 75A, 2-legs
Blank = Zero voltage turn on
R = Instantaneous turn on
P = With internal overvoltage protection
Blank = No Over Temperature protection
TA = With Over Temperature Protection and Alarm Output
60 = 48-600 VAC
Required for valid part number
For options only and not required for valid part
number