Datasheet
Page 10
www.sensata.com
Copyright © 2018 Sensata Technologies, Inc.
Series
DRMS
Operating Voltage
48: 200-480 VAC
Control Voltage
D: 10-30 VDC
Load Current per Phase
9: 9 Amps
Function
1: Reversing Contactor with Overload Protection
2: Reversing Contactor with Soft Start, Soft Stop and Overload Protection
3: Reversing Contactor with Soft Start, Soft Stop, Overload Protection and Mains Isolating Relay
ORDERING OPTIONS
Example : DRMS48D91
DRMS
48 D 9 1
AGENCY APPROVALS & CERTIFICATIONS
Tested and Certified According To
E116949
UL 508 and C22.2 No.14-13
With restrictions at motor switching power:
- ANSI/UL 60947-1, 3rd Edition (Low-Voltage Switchgear and Controlgear Part1: General rules)
- ANSI/UL 60947-4-2, 1st Edition (Low-Voltage Switchgear and Controlgear Part 4-2: Contactors and Motor-Starters - AC Semiconductor Motor
Controllers and Starters)
- CAN/CSA-C22.2 No. 60947-1-07, 1st Edition (Low-Voltage Switchgear and Controlgear - Part1: General rules)
- CSA-C22.2 No. 60947-4-2-14, 1st Edition (Low-Voltage Switchgear and Controlgear - Part 4-2: Contactors and Motor-Starters - AC Semiconductor
Motor Controllers and Starters
DRMS Motor Circuit Ratings
Per UL508, CSA C22.2 No. 14-13
Network Voltage Ambient Temperature FLA / LRA
200-480VAC, 3-phase, 50/60Hz
40ºC 7.6 / 45.6
50ºC 4.8 / 28.8
60ºC 2.1 / 12.6
Per UL 60947-4-2, CSA 60947-4-2
200-300VAC, 3-phase, 50/60Hz
40ºC 7.6 / 45.6
50ºC 4.8 / 28.8
60ºC 2.1 / 12.6
301-480VAC, 3-phase, 50/60Hz 60ºC 2.1 / 12.6