Brochure

solicon
DRC Series
Americas
Tel.: +1 (877) 502 5500
sales@crydom.com
EMEA
Tel.: +44 (0) 1202 606030
sales-europe@crydom.com
Asia
Tel.: +86 (0) 21 6065 7725
sales-cn@crydom.com
DRC Series Contactor
DIN Rail Mounted 3 Phase & Reversing Solid State Contactors
7.6 Amp Motor Controller rated Solid State Contactor
Load voltage range up to 530 VAC
Fits standard 35 mm DIN rail
LED input status indicator
AC or DC control
Zero crossing (resistive loads) or instantaneous turn-on (inductive loads) output
Built in Overvoltage Protection
Ultra-efficient thermal management design (Patented)
C-UL-US Listed, IEC Rated, CE & RoHS Compliant, Horsepower Rated
Start / Stop
Reversing
Output Specifications
DRCa3R48xxx
(A)
DRC3Pxxxx
Normally Open Suffix 2x, 1x
Option A
Input Specifications
(A)
Solid State Auxiliar Contacts
(A)
Operating Voltage Range (47-63 Hz) [Vrms]
Transient Overvoltage [Vpk] (B)
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Maximum Off-State dv/dt @ Maximum Rated Voltage [V/µsec]
Load Current, Resistive UL508/AC51 @ 40°C [Arms] (C)
Load Current, Motor Controller UL508/AC53 @ 480VAC [Arms] (C)
Minimum Load Current [Arms]
Maximum Surge Current [Apk] 1 Cycle 60Hz
Maximum Surge Current [Apk] 1 Cycle 50Hz
Maximum I
2
t for Fusing (8.33msec)[A
2
sec]
Maximum I
2
t for Fusing (10msec)[A
2
sec]
Maximum On-State Voltage Drop @ Rated Current [Vrms]
Minimum Power Factor (with Maximum Load)
Ratings according to UL 508/IEC60947-4-2 [HP/KW]: 240 VAC
Ratings according to UL 508/IEC60947-4-2 [HP/KW]: 400 VAC
Ratings according to UL 508/IEC60947-4-2 [HP/KW]: 480 VAC
48-530
1200
3
500
5
4.8
0.15
750
716
2330
2560
1.15 per channel
0.5
1 / 0.75
2 / 1.5
3 / 2.2
48-530
1200
3
500
7.6
7.6
0.15
750
716
2330
2560
1.15 per channel
0.5
2 / 1.5
3 / 2.2
5 / 3.7
48-415
1200
5
500
7.6
7.6
0.15
750
716
2330
2560
1.15 per channel
0.5
2 / 1.5
3 / 2.2
-
48-510
1600
5
500
7.6
7.6
0.15
625
597
1621
1779
1.15 per channel
0.5
2 / 1.5
3 / 2.2
5 / 3.7
DRC3Pxxxx2 DRC3R40xxx
Control Voltage Range
Minimum Turn-On Voltage (D)
Must Turn-Off Voltage
Minimum Input Current (for On-State) [mA ± 10%]
Maximum Input Current [mA ± 10%]
Nominal Input Impedance
Maximum Delay to Turn-On [msec] (E)
Maximum Turn-Off Time [msec] (F)
208-265 VAC
208 VAC
60 VAC
5.5
7.7
36 K
30
30
90-140 VAC
90 VAC
20 VAC
5
8
16.4 K
30
30
18-30 VAC / VDC
18 VAC / VDC
7 VAC / VDC
10
22
1.3 K
20
30
Option B Option D
Operating Voltage Range (47-63 Hz) [Vrms]
Transient Overvoltage [Vpk]
Maximum Load Current [Arms]
Minimum Load Current [mA]
Maximum Surge Current [Apk] 1 Cycle 60Hz
Maximum Surge Current [Apk] 1 Cycle 50Hz
Maximum I
2
t for Fusing (8.33msec)[A
2
sec]
Maximum I
2
t for Fusing (10msec)[A
2
sec]
Maximum Off-State Leakage Current @ Rated Voltage
Maximum Off-State dv/dt @ Maximum Rated Voltage [V/µsec]
Maximum Delay to Turn-On [msec] (E)
Maximum Turn-Off Time [msec] (F)
18-280
600
1
5
40
38
6.7
7.2
0.1 mArms
500
20
30
Normally Closed Suffix x1
18-280
600
1
5
40
38
6.7
7.2
5 mA
500
80
30
DRC3
General Specifications
(A)
Dielectric Strength, Input-Output to Baseplate (50/60Hz) [Vrms] (G)
Minimum Insulation Resistance (@ 500 VDC) [Ohm]
Maximum Capacitance, Input/Output [pF]
Ambient Operating Temperature Range [ºC]
Ambient Storage Temperature Range [ºC]
LED Status Indicator (color) (H)
Short Circuit Current Rating [KA] (J)
Weight (typical)
Housing Material
Housing Color
Humidity
3750
10
9
20
-30 to 80
-40 to 100
Forward (Green) / Reverse (Amber)
100
2 Controlled Legs (6.940 oz [196.7 g]) / 3 Controlled Legs (8.050 oz [228 g])
UL94 V-0
Black and Light Gray
85% Non-Condensing