SPECIFICATIONS
Output
(2)
Description 25A 30A
Operating Voltage (47-440Hz) [V
RMS
]
48-600 48-600
Transient Overvoltage [Vpk]
(3)
1200 1200
Maximum Off-State Leakage Current @ Rated Voltage
[mA
RMS
]
1 1
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/
μsec]
500 500
Load Current, General Use UL508/LC A IEC62314 @ 40°C
[A
RMS
]
25 30
Load Current, Motor Starting UL508 FLA/LC B IEC62314 @
40°C [ARMS]
12/6.8 12/6.8
Minimum Load Current [mA
RMS
]
100 100
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
716/750 716/750
Maximum On-State Voltage Drop @ Rated Current [V
RMS
]
1.15 1.20
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec]
2563/2343 2563/2343
Minimum Power Factor (at Maximum Load)
0.5 0.5
Motor Rating UL 508: 120 VAC / 240 VAC / 480 VAC [HP]
1.5/3.0/7.5 1.5/3.0/7.5
Motor Rating IEC62314: 240 VAC / 400 VAC / 500 VAC [kW]
1.5/3.0/4.0 1.5/3.0/4.0
ORDERING OPTIONS
Example : DR6760A25RPTA
Description of part number example
Operating Voltage
Control Voltage
Family
Rated Load Current
Switching Type
Overvoltage Protection
D = 4-32 VDC (4-28 VDC for TA option)
A = 90-280 VAC/VDC
DR67 60 x xx x
25 = 25A, 3-legs
30 = 30A, 2-legs
Blank = Zero voltage turn on
R = Instantaneous turn on
P = With internal overvoltage protection
48-600 VAC
Over Temperature Protection
(1)
Blank = No Over Temperature protection
TA = With Over Temperature Protection and Alarm Output
P
xx
Required for valid part number
For options only and not required for valid part
number