Datasheet

INPUT SPECIFICATIONS
(2)
DRxxExxDRxxBxxDRxxDxxDescription
Control Voltage Range (5) 4-32 VDC 200-265 Vrms 18-36 Vrms (1)
Minimum Turn-On Voltage 4.0 VDC 200 Vrms 18 Vrms
Must Turn-Off Voltage 1.0 VDC 40 Vrms 4 Vrms
Minimum Input Current for [mA] (6) 9 2.5 3.5
Maximum Input Current for [mA] (6) 11 3.3 8
1/2 Cycle 20 msec 20 msec
Maximum Turn-on Time [msec] (7) (8)
1/2 Cycle 30 msec 30 msec
Maximum Turn-off Time [msec] (9)
22/16 AWG 22/16 AWG 22/16 AWG
GENERAL SPECIFICATIONS
(2)
Description Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) 4000 Vrms (10)
Minimum Insulation Resistance (@ 500 VDC)
Maximum Capacitance, Input/Output 10 pF
Ambient Operating Temperature Range -30 to 80 °C
Ambient Storage Temperature Range -30 to 100 °C
Recommended Terminal Screw Torque Range
10
9
Ohm
OUTPUT SPECIFICATIONS DC Output
(2)
Description DR06D06 DR10D06 DR06D12 DR10D12
Operating Voltage [VDC] 1-60 1-100 1-60 1-100
Maximum Load Current [Adc] (3) 6 6 12 12
Minimum Load Current [mAdc] 2.5 2.5 2.5 2.5
0.1 0.1 0.1 0.1
0.6 0.6 0.6 0.6
Maximum Off-State Leakage Current @ Rated Voltage [mA]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
60 60
On-State resistance at rated current [Ohms]
0.1 0.1
Min/Max stranded wire
22/14 AWG 22/14 AWG
22/14 AWG 22/14 AWG
1.94 oz. (55g) 1.76 oz. (50g)
Min/Max solid wire
Weight (typical)
Maximum Surge Current (10ms) [Apk]
100 100
0.45
22/14 AWG
22/14 AWG
3.17 oz (90g)
0.45
22/14 AWG
3.17 oz.(90g)
22/14 AWG
Min/Max stranded/solid wire
DRxxAxx
90-140 Vrms
90 Vrms
10 Vrms
3
5
20 msec
30 msec
22/16 AWG
GENERAL NOTES
(2) All parameters at 25°C unless otherwise specified.
(1) E option is UL certified for AC control voltage, but it works also with 18-36 VDC input range.
(3) See Derating curves
(4) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
(5) DC control includes reverse polarity protection.
(6) Input circuitry incorporates active current limiter.
(7) Turn-on time for DC control random turn-on versions is 0.1 msec.
(8) Turn-on time for DC output 600
µsec.
(9) Turn-off time for DC output 300
µsec.
(10) 2500Vrms for DC output.
LC A, Resistive or Slightly Inductive Load Ratings: 12A @40°C ambient for DR24x12, 12A @ 40°C ambient for DR48x12
LC A, Resistive or Slightly Inductive Load Ratings: 6A @ 40°C ambient for DR24x06, 6A @ 40°C ambient for DR48x06
LC B, Motor Loads Ratings: 0.75KW @ 240VAC for DR24x06 and 2.2KW @ 480VAC DR48x12
LC B, Motor Loads Ratings: 0.375KW @ 240VAC for DR24x06 and 1.5KW @ 480VAC DR48x12
Standards of Compliance
IEC 62314
Shock and Vibration (Applies to all part numbers)
Vibration Resistence according to IEC 60068-2-6: 0.35mm and 0.75mm Amplitude over 10-55 Hz
Shock Resistance according to IEC 60068-2-27: 15g/11ms
EMC (Applies to all part numbers)
IEC 61000-4-2: Electrostatic Discharge- Level 3
IEC 61000-4-4: Electrically Fast Transients- Level 3
IEC 61000-4-5: Electrical Surges- Level 3
ANSI / ISA 12.12.01-2013
Nonincendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Division 1 and 2 Hazadous (classified) locations
This equipment is open-type device and is meant to be installed in an enclosure suitable for the enviroment such that the equipment is only accesible with the use of a tool
suitable for use in Class 1, Division 2, Group A,B,C and Hazardous locations, or Nonhazardous locations only
WARNING-Explosion Hazard- Do not disconnect equipment while the circuit is live or unless the area is known to be free of ignitable concentrations
WARNING-Explosion Hazard- Substitution of any component may impair suitability for Class I, Division 2
4.4-7.0 in-lb (0.5-0.8Nm)
Datasheet
DIN Rail Mount
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.