Datasheet

53TP Series IP20
• Three-phase solid-state relay; Ratings 25A , 50A per phase @ 48-530 VAC
• 2 package styles IP20 or IP00
(See IP00 spec sheet for more information)
• SCR output for heavy industrial loads
• AC or DC control
• Zero-crossing (resistive loads) or random-fire (inductive loads) output
• LED input status indicator
• Transient protection built in
PRODUCT SELECTION
Control Voltage 25A 50A
90-140 VAC B53TP25C B53TP50C
180-280 VAC C53TP25C C53TP50C
4-32 VDC D53TP25C D53TP50C
18-36 VAC E53TP25C E53TP50C
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
Description 25 A 50 A
Operating Voltage (47-63Hz) [Vrms] 48-530 48-530
Transient Overvoltage [Vpk] 1200 1200
Maximum Off-State Leakage Current @ Rated Voltage [mArms] 3 3
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2) 500 500
Maximum Load Current per phase [Arms] (3) 25 50
Minimum Load Current per phase [Arms] 0.1 0.1
Maximum 1 Cycle Surge Current (50/60Hz) [Apk] 275-300 710-750
Maximum 1 Second Surge Current 50/60 Hz [Apk] 85 150
Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.35 1.35
Thermal Resistance Junction to Case (Rjc) [°C/W] 0.24 0.12
Maximum 1/2 Cycle I²t for Fusing (50/60 Hz) [A² sec] 380-370 2520-2320
Minimum Power Factor (with Maximum Load) 0.5 0.5
UL/IEC 60947 Motor Control Ratings at 120V [HP/KW] (4) 0.75/0.56 1.5/1.11
UL/IEC 60947 Motor Control Ratings at 240V [HP/KW] (4) 1/0.74 3/2.22
UL/IEC 60947 Motor Control Ratings at 380V [HP/KW] (4) 2/1.48 5/3.7
UL/IEC 60947 Motor Control Ratings at 480V [HP/KW] (4) 3/2.22 7.5/5.55

Summary of content (5 pages)