Datasheet
Datasheet
I/O Modules
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
GMS SERIES 17.5mm OUTPUT MODULES
•
DIN Rail Mountable Single Point Output Modules (35mm DIN)
•
UL and cUL Recognized, CE Compliant
•
Zero Voltage or Random Turn-On for AC Modules
•
4kV Optical isolation with LED Indicator
•
AC Ratings 12-280 VAC, 5A. DC Output 5-60 VDC, 3A
•
Industry standard Color Coding Black (AC Output) Red (DC Output)
•
Barrier Strips Accept 14 to 28 AWG Wire.
SPECIFICATIONS
Input
401031488010314850103148rebmuN traP
Nominal Voltage [VDC] 4-32 4-32 4-32
Minimum Voltage [VDC] 4 4 4
Maximum Voltage [VDC] 32 32 32
Drop-out Voltage [VDC] 1.0 1.0 1.0
Maximum Current [mA] (2) 22 22 22
Resistance Current Regulated Current Regulated Current Regulated
Output
84130105 84130108 84130104
Nominal Line Voltage 240 VAC 240 VAC 5-60 VDC
Minimum Line Voltage 12 VAC 12 VAC 5 VDC
Maximum Line Voltage 280 VAC 280 VAC 60 VDC
Max Off-State Voltage (3) 800 Vpeak 800 Vpeak 60 VDC
Max Off-State Leakage (4) 0.1mArms 0.1mArms 10 uA
Static Off-State dv/dt (5) 50 V/usec 50 V/usec N/A
Maximum Rated On-State Current (6) 5.0 Arms 5.0 Arms 3.0 A
Minimum On-State Current 50 mArms 50 mArms 10 mA
Max Surge Current (7) 350 Apeak 350 Apeak 5.0 A
On-State Voltage Drop or Resistance (8) 1.85 V 1.85 V 1.6 V
Maximum Turn-On Time [msec] (9) 8.33 0.1 0.05
Maximum Turn-Off Time [msec] (9) 8.33 8.33 0.05
Input/Output Isolation Voltage (10) 4000 Vrms 4000 Vrms 4000 Vrms
Input/Output Capacitance 6 pF 6 pF 4 pF
Operating Temperature Range -30 to 80°C -30 to 80°C -30 to 80°C
Storage Temperature Range -40 to 100°C -40 to 100°C -40 to 100°C
Line Frequency Range 47 to 63 Hz 47 to 63 Hz DC
Weight 1.1 oz. (31.2g) 1.1 oz. (31.2g) 1.1 oz. (31.2g)
GENERAL NOTES
(1)
Specifications apply to an ambient temperature of -30 to 80 °C unless otherwise noted.
(2)
Modules are current limited +/- 10% at 25°C.
(3)
Maximum 1 minute duration for AC modules when applied as a DC voltage rather than
Peak AC voltage.
(4)
At maximum line voltage, 25°C for AC modules and 80°C for DC module.
(5)
Minimum dv/dt per EIA/NARM RS443, method RS397. dv/dt ratings do not apply to DC module.
(6)
At 25°C, derate AC modules by 50 mA/°C to 80°C; derate DC module by 21.5mA/°C to 80°C.
(7)
At 25°C, maximum duration: 1 AC cycle for AC modules, 1 s
econd for DC module.
(8)
At maximum rated on-state current and 25°C.
(9)
At maximum line voltage, maximum rated output current, nominal input voltage, 25°C.
(10)
At 25°C for 1 second maximum duration.
(1)