General Accessories
SENSAPHONE
Monitoring Sensor
Specifications
Description
Package Contents
Specifications
Description
Package Contents
(1) Air quality sensor
(1) Installation instructions
Air Quality Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FGD-0066
Measurement:
Solid State TGS VOC sensor
Sample Method:
Flow through
Operating Temp Range:
32° to 122°F (0° to 50°C)
Housing:
White plastic
Dimensions:
2.8” x 4.7” x 1.25”
71mm x 119mm x 32mm
Compatibility:
1400, 1800, 2800, 2000,
Express II, SCADA 3000,
WEB600 and CELL682
*Specifications subject to change
without notice
The Sensaphone Indoor Air Quality sensor will allow monitoring of levels of pollution from
0–100% with any Sensaphone that will accept a 4-20mA input signal. The Air Quality sensor
uses a tin dioxide semiconductor sensor to detect oxidizable gases and is specially designed
to have high sensitivity to gaseous organic materials which are components of indoor air
pollutants. These air contaminants include cigarette smoke, cooking exhaust, automobile
exhaust, solvents and many others. Requires a 24VDC power supply. (Part # FGD-0053)
Air Quality Sensor
Carbon Monoxide Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FGD-0065
(1) CO sensor
(1) Installation instructions
CO Range:
0-300 PPM
Accuracy:
± 5% PPM
Operating Temp Range:
-4° to 122°F (-20° to 50°C)
Coverage Area:
50’ radius
Housing:
Black plastic
Dimensions:
7.2” x 4.9” x 1.7”
Compatibility:
1400, 1800, 2000, 2800,
Express II, SCADA 3000,
WEB600 and CELL682
*Specifications subject to change
without notice
Carbon Monoxide is a highly toxic gas that has no color or odor. The Sensaphone Carbon
Monoxide sensor will allow you to monitor CO levels from 0-300 ppm with any Sensaphone
that will accept a 4-20mA input signal. The 1” x .5” LCD displays the PPM and menu
parameters. The sensor will require a 24VDC power supply to operate (Part # FGD-0053).
Carbon Monoxide (CO) Sensor
General Accessories
SENSAPHONE
Monitoring Sensor
Specifications
Description
Package Contents
Specifications
Description
Package Contents
(1) J Type Thermocouple
Converter
(1) Instruction Booklet
J Type Thermocouple / 4–20mA Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FGD-0220
Thermocouple Type:
J (not included)
Output Range:
4 to 20mA
Input Temp Range:
-148° to 572°F
-100° to 300°C
Mechanical Format:
DIN Rail (Mounting)
Accuracy:
0.08%
Supply Voltage:
15 to 30V DC
(+ 24V DC Nom)
Dimensions:
2.95” x .89” x 4.13”
75mm x 23mm x 105mm
Compatibility:
1400, 1800, 2800, 2000,
Express II, SCADA 3000,
WEB600, CELL682
*Specifications subject to change
without notice
The thermocouple to 4-20mA converter is useful when monitoring very high or very low
temperatures that can not be monitored with a standard Sensaphone temperature sensor. Each
thermocouple input module provides a single channel of thermocouple input which is filtered,
isolated, amplified, linearized and converted to a 4-20mA output. Isolation is provided by
transformer coupling, using a proprietary technique to suppress transmission of common mode
spikes or surges. The modules have excellent stability over time.
J Type Thermocouple / 4-20mA Converter
Multi–Point Wireless I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FGD-0205
(1) Transmitter
(1) Receiver
(2) 24VDC power supplies
(2) Antennas
(1) Instruction booklet
Inputs transmitter:
Analog: 4mA - 20mA
Number of Digital Inputs: 2
Voltage Range: 5-30V
Analog Output (receiver)
4-20mA, 750Ω max
Digital output (receiver)
Contact Type: 2 NO/NC
Power Supply
Supply Voltage:12V DC -
30V DC
General:
Dimensions:
3.89” x .68” x 4.5”
Mounting: DIN–rail mount
UL, USA / Canada: Class I,
Div. 2, Groups A, B, C, D
Compatibility:
1400, 1800, 2800, 2000,
Express II SCADA 3000,
WEB600 and CELL682.
*Specifications subject to change
without notice
The multi-point wireless I/O system is ideal if you need to connect one or two dry contacts
and/or a 4-20mA transducer to a Sensaphone that is too far (or too expensive) to run cable. The
system will replicate these sensors up to a distance of 600’ indoors or up to 4 miles line of site
(flat terrain, raised antennas). The system includes a matched 1 Watt 900MHz transmitter and
receiver. Two 24V power supplies and omni-directional antennas are included. Built-in leds
indicate RF link and dry contact status.
Multi–Point Wireless I/O