Product guide

Sensaphone
Monitoring Systems
Sensaphone
Monitoring Systems
20 WWW.SENSAPHONE.COM
WWW.SENSAPHONE.COM
21
SENSAPHONE
Monitoring Solution
CELL682
Remote Monitoring
Via Cellular
Description Part Number
CELL682 w/ Clear Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .FGD-CELL682-CD
CELL682 w/ Solid Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FGD-CELL682-SD
CELL682 w/ Clear Door for Canada . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FGD-CELL682-CD-CAN
CELL682 w/ Solid Door for Canada . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FGD-CELL682-SD-CAN
Sensaphone CELL682 One year of communication service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FGD-CELL1Y
*Contact us for availability and part numbers for other regions
14 Inputs
• 6 Analog
Temp
4-20mA
• 8 Dry Contact
Voice
Text
Email
Up to 24 total
Cellular
Communication
Battery
Backup
Web Status
Web History
2 Outputs
Web Server
Description
The Cell682 uses standard cellular technology to communicate
with the Sensaphone servers. If a telephone line is not already in
place, the cellular communications in the Sensaphone Cell682 can
provide a convenient, reliable, and cost effective method to monitor
a remote facility.
The Sensaphone Cell682 provides an assortment of sensor input
options to handle many different types of sensors and conditions
to monitor. Two relay outputs are also included in the
Cell682 for local
control.
Enclosed in a sealed,
weatherproof,
lockable enclosure, the Cell682 is suitable for use in harsh or corrosive
environments. LED’s on the face of the unit afford local indication of
alarm and status conditions.
When an input channel detects an alarm there is an immediate
communication from the CELL682 to the Sensaphone servers to process
the alarm. The appropriate people are then contacted immediately via
e-mail, cell phone and pager text messages or custom voice phone calls.
A website is provided for status, history, alarm response programming,
and manual output control.
Communication:
GSM Cellular Wireless
Technology
90+% Wireless Coverage
Alarm Delivery:
24 Programmable destinations
E-Mail Alarm Delivery
SMS Text Message
Custom Voice Phone Call Alarm
Delivery
Inputs:
Six Analog 4-20mA Inputs
Eight Contact Closure Inputs
Run Time Accumulation
Outputs:
Two Mechanical Relays
Can Automatically Switch Based
On Alarms
Built In Duplex Pump Control
Logic
Peer to Peer Control Logic
Local indicators:
Alarm Status
Wireless Account Registered
Wireless Signal in Range
Battery Backup Status
Power Status
Output States
Power
External 110VAC transformer
220VAC available
Enclosure:
NEMA 4-X
Operating conditions:
-22° to 140°F, -30° to 60°C
NEW
for
2011
Why choose the
CELL
682
?
• Wireless Cellular, no need for
phone line
• Website to access status
and programming
• Multiple Analog 4-20mA inputs
• Output control
• Supports remote peer to
peer control
The Cell682 can be placed at a
remote, unmanned facility to
detect a variety of potential
equipment problems, and can
even perform some output control.
The Cell682 has 8 Dry Contact inputs that can be used
to monitor Normally Open (N.O.) or Normally Closed
(N.C.) sensors and 6 Analog inputs that can be used
to monitor 2.8K or 10K Thermistors (temperature) or
4–20mA transducers.
Check status, make programming changes,and even
control outputs from any internet connected computer
An alarm history log is available on the web page to
provide details on alarms that have occurred and who
acknowledged them
Its built-in wireless
technology means
you won’t need a
telephone line to
communicate with
the unit.