Instructions / Assembly

APPENDIX F: 1800 Quick Reference Guide
97
Tone or Pulse Dialing Dialing method—touch-tone or pulse
[SENSOR ON/OFF] + [PHONE NUMBER T/P]
Tone or Pulse Default=Tone
Alarm Programming
Alarm Limits High and low temperature alarm limits
[SET] or [WHAT IS] + [ALARM LIMITS]+ [Zone #]
Min: -109°F/-65°C Max:168°F/76°C Default=Low: 0°F; High:100°F
4–20mA Table Range Defines upper and lower range of 4–20mA sensor
[SET] or [WHAT IS] + [TABLE RANGE] + [zone #]
Min: -10,000, Max: 10,000 Default=Low: 0, High:100
4–20mA Alarm Limits High and low alarm limits
[SET] or [WHAT IS] + [LOW LIMIT] or [HIGH LIMIT] + [zone #]
Min: -10,000, Max: 10,000 Default=Low: 0, High: 100
Zone Calibrate Offset correction factor [temp/4-20mA]
[SET] or [WHAT IS] + [CALIBRATE] + [zone #]
Min: -15°/-100, Max: 15°/100 Default=0
Auto� Zone Configuration Automatically configures all zones.
[SET] + [STATUS/CONFIGURE] + 0
Default=n/a
Manual Zone Configuration To configure an individual zone type (required for 10K Temp)
[SET] + [STATUS/CONFIGURE] + [zone #] + [type]
1 = NO, 2 = NC, 3 = 2.8K Temp, 4 = 10K 5 = 4–20mA
Default=n/a
Recognition Time Zones 1–4 Length of time a fault condition must exist to trip an alarm
[SET] or [WHAT IS] + [REC TIME] + [zone #]
Min:00:00, Max: 540:00 Default=00:03 (min:sec)
Rec Time: Power Failure Length of time the power must be off to trip an alarm
[SET] or [WHAT IS] + [REC TIME] + [POWER]
Min: 00:00, Max: 540:00 Default=05:00 (min:sec)
Rec Time: High Sound Level Length of time the sound must be high to trip an alarm
[SET] or [WHAT IS] + [REC TIME] + [SOUND]
Min: 00:05, Max: 00:60 Default=00:08 (min:sec)
Sound Level Alarm Sensitivity Microphone sensitivity for high noise level alarm
[SET] or [WHAT IS] + [CALIBRATE] + [SOUND]
Min: 1 (most), Max: 160 (least) Default=32
Enable/Disable Zone Turns zone alarm detection on or off
[SENSOR ON/OFF] + [zone #]
On or Off Default=Enabled (on)
Power Alarm Enable/Disable Turns power alarm detection on or off
[SENSOR ON/OFF] + [POWER]
On or Off Default=Enabled (on)
Sound Alarm Enable/Disable Turns high sound level alarm detection on or off
[SENSOR ON/OFF] + [SOUND]
On or Off Default=Enabled (on)