Instructions / Assembly

APPENDIX C: Troubleshooting the 1800
89
PROBLEM 2
The zone input is not reading correctly.
a) No power connected to the transducer: Connect a power supply as
shown in Chapter 2.
b) Incorrect wiring: Inspect wiring. Make sure polarity is correct as shown
in Chapter 2.
c) The table range is incorrectly programmed: Program the table range for
the calibrated range of the transducer.
d) The input is not configured for 420mA: Configure the zone for
4–20mA. Refer to Chapter 4
e) Multiple devices connected in loop: The 1800’s zone is single-ended
and terminates to ground. Because of this, the 1800 must be the last
device in the loop, and in some cases the ONLY device. For certain
installations, it may be necessary to use a signal isolator.
SOUND LEVEL MONITORING:
PROBLEM 1
False high sound alarms occur frequently.
a) The programmed sound sensitivity results in over-sensitivity to non-
alarm sound as well as alarm sound: Reprogram the sound sensitivity
(calibration). Refer to Chapter 4.
b) Sound Recognition Time is too short: Lengthen the sound Recognition
Time. Refer to Chapter 4.
PROBLEM 2
High sound does not cause an alarm.
a) The microphone is not close enough to the high sound source, or the
programmed sound setting results in a lack of sensitivity to high sound:
Move the microphone closer or reprogram the sound sensitivity. Refer to
Chapter 4.
b) No remote microphone (optional) connected to the unit: Connect a
remote microphone to the Mic terminals.
OTHER MONITORING:
PROBLEM 1
Alarm status of a zone is incorrect.
Incorrect zone configuration.
Reconfigure the zone. See Chapter 4.