APPENDIX A: Checking Your Sensaphone 1800 for Proper Operation
83
APPenDIX A: CHeCKInG
YoUR sensAPHone 1800
foR PRoPeR oPeRAtIon
We recommend that you test your Sensaphone 1800 weekly to be sure it is
functioning properly. This will ensure that when a problem arises the 1800
will be ready to alert the appropriate personnel. Sensaphone also recom-
mends you keep a log of performed tests, and has provided you with a Test
Log template at the back of this manual.
There are several tests that can be performed:
1. Call the unit and listen to the Status Report. This will test the units
ability to answer the phone and speak a message. It will also verify
that the inputs are reading properly, the alarm conditions are OK, the
electricity is on, the microphone is functioning (optional), and that the
batteries are OK.
2. Create a test alarm on each input and allow the unit to contact all
programmed telephone numbers. This will make sure that the 1800 is
programmed properly. It will also prepare personnel to respond appro-
priately when they receive a call from the 1800. Listed below are sug-
gestions on how to trip test alarms:
• Temperature sensors: Heat or cool the sensor.
• Motion sensors: Have someone walk in front of the sensor.
• Door/window sensors: open the door/window.
• Water sensors: Apply a small amount of water beneath the sensor or use
a wet towel and touch it to the sensor probes.
• Humidity sensors: Raise the humidity around the sensor by holding a
cup of very hot water beneath the sensor.
• NO/NC Contacts: Open or close the contact.
Allow the unit to contact all programmed telephone numbers. This will
make sure that the 1800 is programmed properly. It will also prepare per-
sonnel to respond appropriately when they receive a call from the 1800.
3. Test the batteries by unplugging the AC adapter and making sure that
the 1800 continues to function. Check that the BATTERY OK LED
remains on steady. Press WHAT IS, then STATUS on the keypad, and
listen to the status report. Make sure the report states that “power is
off” and “battery is OK.” Keep the AC adapter unplugged so that a
Power Failure alarm occurs. Allow the unit to dial all programmed
telephone numbers while running on battery backup. Plug in the AC
adapter after the unit has finished dialing all of the telephone numbers.