Instructions / Assembly
CHAPTER 6: CONTROLLING THE OUTPUT
73
CHAPteR 6: ContRoLLInG
tHe oUtPUt
The 1800 includes a relay output that can be used to control a light, siren,
or other device. The output is a Form-C Normally Open/Normally Closed
mechanical relay and is rated for up to 120VAC 2A. A sample wiring dia-
gram is shown below:
Figure 1: Relay output connected to alarm
The output can be programmed to operate in one of 7 automatic modes or
it can operate in manual mode (default). The 7 automatic modes allow the
output to automatically turn on and off based on individual alarms or any
alarm. In manual mode the output is controlled via keypad command or
remotely via touch-tone phone (See Chapter 7). A description of each mode
is shown below:
AUTOMATIC MODES
Mode 1: Output on when zone 1 goes into alarm. Off when alarm is
acknowledged.
Mode 2: Output on when zone 2 goes into alarm. Off when alarm is
acknowledged.
Mode 3: Output on when zone 3 goes into alarm. Off when alarm is
acknowledged.
Mode 4: Output on when zone 4 goes into alarm. Off when alarm is
acknowledged.
Mode 5: Output on when zone 5 goes into alarm. Off when alarm is
acknowledged.
Mode 6 : Output on when zone 6 goes into alarm. Off when alarm is
acknowledged.