The 1800 will recite the programmed Reset Time for that Zone. If the Reset
Time is set to 0 minutes the 1800 will say “Disabled.
ZONE CALIBRATION
Due to tolerance variations or other factors, you may need to program
an offset to calibrate the sensor. The offset can range from -15 to +15 for
Zones configured as temperature, and -100 to +100 for Zones configured as
4–20mA. Setting a positive number will add that number to the Zone read-
ing. Setting a negative number will subtract the programmed value from the
Zone reading. For instance, if a temperature sensor consistently reads two
degrees high, you could use the calibration feature to adjust that tempera-
ture down two degrees. To make a value negative, precede the value with
the [RINGS/TAD/*] Key.