Instructions / Assembly

CHAPTER 4: ZONE PROGRAMMING
35
3. Press the corresponding Zone key (1–8). 1800 will say the programmed
value.
1
CALL
DELAY
4
MAX
CALLS
7
RECOGNITION
TIME
8
RESET
TIME
5
ALARM
LIMITS
6
2
VOICE
REPS
3
INTERCALL
TIME
CALIBRATE
RESET TIME
The Reset Time allows your Sensaphone to reset the dialing sequence if an
alarm continues to exist well after it has been acknowledged. For example,
suppose the Reset Time for Zone 1 is programmed for 2 hours. If an alarm
occurs on Zone 1 at 6PM and is acknowledged at 6:15PM and the alarm
condition is never corrected, then at 8:15PM (2 hours later) the Sensaphone
will “reset” the alarm and begin the notification process all over again.
This feature should be used for all critical monitoring applications where a
prolonged alarm condition could cause catastrophic results.
The Reset Time can be programmed between 30 and 1440 minutes for
each zone. The default setting is 0 minutes - which disables the feature. The
reset time is defined as the time allowed for an acknowledged alarms fault
condition to be corrected before the alarm resets and begins the message
delivery process all over again.
The Reset Time must be programmed individually for each Zone, includ-
ing the Power and Sound alarm.
1. Press the SET key.
SET
2. Press the RESET TIME key.
8
RESET
TIME
The 1800 will say “Enter Zone Number.