Instructions / Assembly
CHAPTER 4: ZONE PROGRAMMING
33
2. Press the RECOGNITION TIME key.
7
RECOGNITION
TIME
1800 will say “Enter Zone Number.”
3. Press the corresponding Zone key (1–8), Power(0), or Sound (9).
1
CALL
DELAY
4
MAX
CALLS
7
RECOGNITION
TIME
8
RESET
TIME
0
ID
POWER
9
LISTEN TIME
SOUND
5
ALARM
LIMITS
6
2
VOICE
REPS
3
INTERCALL
TIME
CALIBRATE
The 1800 will recite the programmed recognition time for that Zone.
ALARM LIMITS
The Alarm Limits determine the level at which a temperature or 4–20mA
Zone has reached the alarm threshold. The input value must exceed
the Alarm Limit to trip an alarm. Each Zone has a programmable Low
and High Alarm Limit. The default settings are Low Limit=0 and High
Limit=100. The range of programming for 2.8K thermistors is -109° to
115°F (-85° to 57°C). The range of programming for 10K thermistors is -87°
to 168°F (-66° to 76°C). For zones configured as 4–20mA, the range of pro-
gramming is -10,000 to 10,000. To make a value negative, precede the value
with the [RINGS/TAD/*]key.
Only Zones configured as temperature or 4–20mA can have Alarm
Limits programmed.
1. Press the SET key.
SET
2. Press the ALARM LIMITS key.
5
ALARM
LIMITS
The 1800 will say “Enter Zone Number.”