Instructions / Assembly

CHAPTER 4: ZONE PROGRAMMING
31
2. Press the TABLE RANGE key. 1800 will say “Enter Zone Number.
TABLE
RANGE
#
3) Press the corresponding Zone number (1–8).
1
CALL
DELAY
4
MAX
CALLS
7
RECOGNITION
TIME
8
RESET
TIME
5
ALARM
LIMITS
6
2
VOICE
REPS
3
INTERCALL
TIME
CALIBRATE
The 1800 will say “Low” and speak the low table value, then it will say
“High” and speak the high table value.
ALARM RECOGNITION TIME
The Alarm Recognition Time is the length of time an alert condition must
be present before a valid alarm exists and dial-out is activated. If a condi-
tion exists and then clears within the recognition time, it is not considered
an alarm. This is useful to prevent nuisance dialouts for momentary alarm
conditions or on self-correcting equipment. Each Zone can be programmed
with a different recognition time, including Power Alarms and Sound Level
Alarms. The default recognition time is 3 seconds for Zones, 5 minutes for
Power, and 8 seconds for Sound level. You may program the recognition
time for Zone and Power Alarms from 0 seconds up to 540 minutes. Sound
Level Alarms may be programmed from 5 to 60 seconds.
When the main power fails, the 1800 will announce out loud “Power
is OFF” every 15 seconds. It will do this regardless of the programmed
recognition time. As a result, when the programmed recognition time is
finally met, the unit will dial immediately and not wait the programmed
Call Delay time. The Power Alarm is the only one treated in this fashion.
1. Press the SET key.
2. Press the RECOGNITION TIME key. 1800 will say “Enter Zone
Number.
7
RECOGNITION
TIME