Instructions / Assembly

CHAPTER 4: ZONE PROGRAMMING
27
The Zones are now considered normal. If a normally closed Zone becomes
open, an alarm will occur. If a normally open Zone becomes closed, an
alarm will occur.
MANUAL ZONE CONFIGURATION
If you would like to program the Zone type (NO, NC, temperature,
4–20mA) without going through the automatic process that scans all Zones,
this command will allow you to configure a single Zone. This command is
useful if you have alarms on other channels and cannot use the automatic
configuration process, or if you wish to configure the Zone type without
actually connecting the sensor.
You MUST use manual configuration for any zone connecting to a 10K
temperature sensor.
1. Press the SET key.
SET
2. Press the CONFIGURE key.
STATUS
CONFIGURE
The 1800 will prompt, “Enter 0 for automatic configuration, enter zone
number for manual configuration.
3. Press the corresponding Zone key (1–8).
1
CALL
DELAY
4
MAX
CALLS
7
RECOGNITION
TIME
8
RESET
TIME
5
ALARM
LIMITS
6
2
VOICE
REPS
3
INTERCALL
TIME
CALIBRATE
The 1800 will say “Enter Mode.
4. Press the key which corresponds to the type of Zone according to the
table below:
1: NO Dry Contact
2: NC Dry Contact
3: 2.8K Thermistor (temperature sensor)
4: 10K Thermistor (temperature sensor)
5: 4–20mA
5. Press ENTER.