Instructions / Assembly
CHAPTER 2: INSTALLATION
21
WIRING SENSORS AND TRANSDUCERS
The 1800 Zones are compatible with NO/NC dry contacts, 2.8K and 10K
thermistors, and 4–20mA transducers. To prevent an alarm from occurring
while wiring the sensors, it is recommended that the zone alarm be disabled
[SENSOR ON/OFF] + [Zone #1–8]. After wiring all of your sensors you
will need to configure the zones using the [SET] + [CONFIGURE] com-
mand. See Chapter Four for more information on Disabling Zone alarms
and Configuring Zones.
Recommended sequence for adding a new sensor:
1. Disable the Zone’s alarm
2. Wire up the sensor
3. Configure the Zone
4. Enable the Zone
If a false alarm occurs while wiring a sensor, you can quickly
acknowledge it by pressing the [ALARM/CANCEL] key. See Chapter
Five for more information on User Acknowledgment Codes.
Temperature: The unit will accept 2.8K or 10K thermistors. These should
be wired to a Zone terminal and the adjacent ground terminal. For rec-
ommended thermistors check the accessory list or thermistor data in the
appendices. Thermistor temperature range:
2.8K: -109°F to 115°F (-85°C to 57°)
10K: -87ºF to 168ºF (-66ºC to 76ºC)
Dry Contact: Only contacts which have no voltage or current applied may
be used. Connect the contact to a Zone terminal and an adjacent ground
terminal. Do NOT try to monitor a contact that switches 120VAC. This will
permanently damage the unit.
4-20mA: A 4–20mA transducer requires you to have an external DC power
supply for the transducer. Connect the positive wire of your transducer to
the positive terminal of your DC power supply. Connect the negative termi-
nal of the transducer to a Zone terminal on the Sensaphone 1800. Connect
the negative terminal from your power supply to the adjacent ground termi-
nal on the 1800.










