Instructions / Assembly
CHAPTER 2: INSTALLATION
19
Smoke
Temperature
Ventilation
Microphone
Dial-out
to Phone
Figure 4: Typical connections from 1800
TURNING THE 1800 ON
Plug the unit’s transformer into a 120VAC 60Hz outlet. Toggle the power
switch on to start the unit. The System-On LED should glow steadily and
the unit will say “Hello.” The unit will not turn on if AC power is not pres-
ent, regardless of the state of the battery.
Note that when the unit is turned off, all programming is retained in non-
volatile memory.
BACKUP BATTERY
The Sensaphone 1800 includes a 6V 3.4AH sealed lead-acid gel-cell
rechargeable battery for system back-up in the event of a power failure. The
battery will provide approximately 24 hours of backup time. Actual backup
time will depend upon the temperature, battery age, dialing activity, and
state of the relay output. The battery is located behind the main panel.
The 1800 will automatically charge the battery whenever the power switch
is turned on and the power transformer is plugged in. The battery should
provide 3–5 years of service, depending on temperature and charge/dis-
charge cycles, before needing replacement. See Appendix B for battery
replacement instructions.