Instructions / Assembly

18
SENSAPHONE 1800 User’s Manual
LOCKING THE ENCLOSURE
The 1800 enclosure can be locked by installing a small luggage-style pad-
lock through the loop on the front door of the enclosure. See Figure below.
Figure 2: Locking the Enclosure
GROUNDING
Connect a heavy gauge (#14AWG) copper wire to the earth ground termi-
nal on the right end of the panel and connect the other end to a ground rod
or metal cold water pipe. It is extremely important that the earth ground
connection be as short as possible. The ground rod should have sufficient
depth to provide a low impedance connection to earth. This connection is
required for the surge/lightning protection circuits to function properly.
Note: Proper earth grounding of the 1800 is required for warranty
coverage.
Ground rods can typically be found at local electrical supply houses and/or
hardware stores. Be sure to contact your state “Call before you dig” hotline
at least two days before you install your ground rod, to insure that it is safe
to install the ground rod in a chosen area.
WIRING CONNECTORS
The 1800 includes compression-type liquid-tight connectors for routing
wires into the enclosure. To use these connectors, turn them counter-
clockwise to loosen (or open-up) the compression washer. Insert all cables
through the two connectors. When finished turn them clockwise to secure
and seal the 1800 from the outside environment. If you don’t have enough
cables to obtain a snug fit you can insert a small piece of soft PVC insula-
tion or rubber tubing to take up the extra space.