Full Product Manual
Chapter 6: Controlling the Output
89
Mode 6: Output on when a Power alarm occurs. Off when alarm is
acknowledged.
Mode 7: Output on when any alarm occurs. Off when all alarms
are acknowledged.
MANUAL MODE
Mode 0: Output controlled manually via keypad command or
touch-tone telephone.
When programmed for Manual mode, the command to switch the
output is:
SENSORON/OFF+OUTPUT.
SENSOR
ON/OFF
OUTPUT
PAUSE
The 1400 will respond “ON” or “OFF” to indicate the state of the
output.
Note: If the 1400 says “Error,” the output is not
programmed for manual mode.
To program the Output Mode:
1. Press the SET key.
SET
2.PresstheOUTPUTkey.
OUTPUT
PAUSE
The 1400 will say “Enter output mode.”