Full Product Manual

Sensaphone 1400 Manual
52
VOICE MESSAGES
The 1400’s digital speech recording feature allows you to record
custom messages for each of the four Zones and an ID Message.
This means that when the 1400 calls you during an alarm, you
will hear a personalized Voice Message identifying the unit and
tellingyouexactlywhatalarmconditionexists.Youcanrecord
a separate message for each of the four Zones. The message can
runamaximumof5seconds.TheIDMessagecanbeamaximum
of 8 seconds. You can shorten the message length by pressing the
ENTER key after reciting the message.
The ID Message is used to identify the unit. This could be a
particularbuildingname,itslocation(addressorcity),orsome
other identifier.
To program the ID Message:
1. Locate the condenser mic.
Mic
SET
1
CALL DELAY
2. Press the SET key.
SET
3. Press the MESSAGE key. The 1400 will say “Enter Message
Number.
MESSAGE
4.PresstheIDkey(number0key).
0
ID
POWER
5. When the unit beeps, begin speaking your message into the
microphone. The unit will say “OK,” when the recording time
has elapsed; then it will play back your recorded message.