Full Product Manual
Sensaphone 1400 Manual
42
To check the alarm limits:
1. Press the WHAT IS key.
WHAT IS
2. Press the ALARM LIMITS key. 1400 will say “Enter Zone Number.”
5
ALARM
LIMITS
3.PressthecorrespondingZonekey(1–4).1400willsaythe
programmed value.
4
MAX CALLS
1
CALL DELAY
2
VOICE REPS
3
INTERCALL
TIME
RESET TIME
The Reset Time allows your Sensaphone to reset the dialing
sequenceifanalarmcontinuestoexistwellafterithasbeen
acknowledged.Forexample,supposetheResetTimeforZone1
is programmed for 2 hours. If an alarm occurs on Zone 1 at 6PM
and is acknowledged at 6:15PM and the alarm condition is never
corrected,thenat8:15PM(2hourslater)theSensaphonewill
“reset” the alarm and begin the notification process all over again.
This feature should be used for all critical monitoring applications
where a prolonged alarm condition could cause catastrophic results.
The Reset Time can be programmed between 30 and 1440 minutes
for each zone. The default setting is 0 minutes - which disables
the feature. The reset time is defined as the time allowed for an
acknowledged alarm’s fault condition to be corrected before the
alarm resets and begins the message delivery process all over again.
The Reset Time must be programmed individually for each Zone,
including the Power and Sound alarm.