Full Product Manual

Sensaphone 1400 Manual
40
1. Press the WHAT IS key.
WHAT IS
2. Press the REC TIME key.
7
RECOGNITION
TIME
1400 will say “Enter Zone Number.
3.PressthecorrespondingZonekey(1–4),Power(0),orSound
(9).
4
MAX CALLS
1
CALL DELAY
2
VOICE REPS
3
INTERCALL
TIME
5
ALARM LIMITS
6
CALIBRATE
9
LISTEN TIME
SOUND
7
RECOGNITION
TIME
0
ID
POWER
8
RESET
TIME
The 1400 will recite the programmed recognition time for that
Zone.
ALARM LIMITS
The Alarm Limits determine the level at which a temperature or
4–20mA Zone has reached the alarm threshold. The input value
mustexceedtheAlarmLimittotripanalarm.EachZonehasa
programmable Low and High Alarm Limit. The default settings are
Low Limit=0 and High Limit=100. The range of programming for
2.8Kthermistorsis-109°to115°F(-85°to57°C).Therangeof
programmingfor10Kthermistorsis-87°to168°F(-66°to76°C).
For zones configured as 4–20mA, the range of programming is
-10,000 to 10,000. To make a value negative, precede the value with
the [RINGS/TAD/*]key.
Only Zones configured as temperature or 4–20mA can have Alarm
Limits programmed.