CONFIGURE TABLE RANGE FOR 4–20MA SENSORS
The 1400 allows you to create a unique linear table for each
4–20mAsensor.TheTableLow(4mA)andTableHigh(20mA)
values are used to define the lower and upper range of your
4–20mAsensor.Forexample,supposeyouareusinga4–20mA
transducer to measure the depth of water in a 15 foot well. Simply
enter a Table Low value of 0 and a Table High value of 15 and the
1400 will scale the Zone to read between 0 and 15. The low and
high table range can be set from -10,000 to +10,000 [Defaults:
low=0, high=100]. To make a value negative, precede the value
with the [RINGS/TAD/*] key.
1. Press the SET key.
SET
2.PresstheTABLERANGEkey.1400willsay“EnterZone
Number.”
TABLE
RANGE
#
3.PressthecorrespondingZonenumber(1–4).1400willsay
“Enter Low Number.”
4
MAX CALLS
1
CALL DELAY
2
VOICE REPS
3
INTERCALL
TIME
4.Usingthenumberkeys,entertheTableLowvalue,thenpress
ENTER.