Full Product Manual

Sensaphone 1400 Manual
32
2.PresstheCONFIGUREkey.
STATUS
CONFIGURE
The 1400 will prompt, “Enter 0 for automatic configuration, enter
zone number for manual configuration.” If you press “0”, the 1400
will scan each Zone input and determine the input type.
The Zones are now considered normal. If a normally closed Zone
becomes open, an alarm will occur. If a normally open Zone
becomes closed, an alarm will occur.
MANUAL ZONE CONFIGURATION
IfyouwouldliketoprogramtheZonetype(NO,NC,temperature,
4–20mA)withoutgoingthroughtheautomaticprocessthatscans
all Zones, this command will allow you to configure a single Zone.
This command is useful if you have alarms on other channels and
cannot use the automatic configuration process, or if you wish to
configure the Zone type without actually connecting the sensor.
NOTE: You MUST use manual configuration for
any zone connecting to a 10K temperature sensor.
1. Press the SET key.
SET
2.PresstheCONFIGUREkey.
STATUS
CONFIGURE
The 1400 will prompt, “Enter 0 for automatic configuration, enter
zone number for manual configuration.