28
When preparing wire for connection to the terminal blocks, strip 4"
ofinsulationfromtheconductor(seefigurebelow).
.25"
Figure 6: Wire stripped for connection
LED INDICATORS
The LEDs provide on-site alarm and status information. Listed
below are descriptions of how the LEDs work.
Zones 1–4, Power and Sound:
LED Off: Zone OK
LEDBlinkingFast:Alarmconditionexistsbut
recognition time has not been met
LEDBlinkingSlowly:Unacknowledgedalarmexists
LEDOn:Acknowledgedalarmexists
Battery:
LEDOn:BatteryOK
LEDBlinking:Batteryconditionlow
LED Off: No battery/critically low battery condition
Output On:
LED On: Output relay on
LED Off : Output relay off
Phone-In-Use:
LEDOn:Unitiscommunicatingonthephoneline
LEDOff:Unitisnotusingthephoneline
System-On:
LED On: System power on
LED Off : System power off