Full Product Manual
Appendix C: Troubleshooting
113
Cause
Incorrect zone configuration.
Solution
Reconfigure the zone. See Chapter 4.
OTHER MONITORING:
Problem 1
Alarm status of a zone is incorrect.
Cause
Programmed Recognition Time is too
short.
Solution
ACpowermaybesubjecttobrief
interruptions. To avoid frequent,
false alarms, increase the power
Recognition Time.
Refer to Chapter 4.
Problem 2
False power-out alarms.
Cause
a)Batteryiseitherincorrectly
installed or drained.
b)Recognitiontimesettingistoo
long.
Solution
To verify proper battery function,
unplug the unit and verify continued
operation using battery only. If unit
ceases to function, replace the battery.
RefertoAppendixB.
Reprogram Recognition Time. Set the
Recognition Time to the minimum
required before a valid alarm
occurs. If possible, test the condition
by deliberately creating an alert
condition. Refer to Chapter 4.
Problem 3
The 1400 does not recognize power failure.