Full Product Manual
Sensaphone 1400 Manual
110
c)Temperaturemayrequire
calibration.
d)Theunitisusingthewrong
temperaturescale(Fahrenheitvs.
Celsius).
After moving or placing the sensor
away from ambient heat sources, the
temperature may be calibrated to
offset inaccurate normal reading by
several degrees.
Refer to Chapter 4.
Verify temperature scale.
Refer to Chapter 4.
TEMPERATURE MONITORING (continued)
Cause
a)Thezoneisconfiguredforthe
wrongtypeofthermistor(i.e.,2.8k
vs.10k)
b)Temperaturesensingmaybe
affected by a source of ambient
heat(ie.,directsunlight,orheat
ductproximity).
Solution
Manually configure the zone as
described in Chapter 4.
Try moving the sensor to a different
location.
Problem 4
Temperature reading is inaccurate.