Error Code Displayed Reason for error Possible remedy
e289 PPC4000 FAULT PPC4000 main CPU timing error Replace PPC4000 (notify Fireye about this error)
e290 PPC4000 FAULT PPC4000 main CPU timing error Replace PPC4000 (notify Fireye about this error)
e291 LESS THAN 2 SERVOS
Less than 2 servos have been assigned to the current
profile
Assign at least to servos (at least one AIR and one
Fuel) to the profiles being used.
e292
to
e318
Unused Unused
e319 NO SENSOR-SETPT DATA Stored “sensor data” is corrupted Pressing RESET will restore factory default values
e320 NO SERVO SETUP DATA Stored “servo data” is corrupted Pressing RESET will restore factory default values
e321 NO DIG I/P DATA Stored “di data” is corrupted Pressing RESET will restore factory default values
e322 NO PASSCODE DATA Stored “passcode data” is corrupted Pressing RESET will restore factory default values
e323 NO P0 DATA Stored “p0 data” is corrupted Pressing RESET will restore factory default values
e324 NO PROFILE1 DATA Stored “profile 1 data” is corrupted Pressing RESET will restore factory default values
e325 NO PROFILE2 DATA Stored “profile 2 data” is corrupted Pressing RESET will restore factory default values
e326 NO PROFILE3 DATA Stored “profile 3 data” is corrupted Pressing RESET will restore factory default values
e327 NO PROFILE4 DATA Stored “profile 4 data” is corrupted Pressing RESET will restore factory default values
e328 NO PROFL SETUP DATA Stored “profile setup data” is corrupted Pressing RESET will restore factory default values
e329 NO KEYPAD SETUP DATA Stored “keypad setup data” is corrupted Pressing RESET will restore factory default values
e330 NO KEY STATES DATA Stored “key states data” is corrupted Pressing RESET will restore factory default values
e331 NO THERML SHOCK DATA Stored “thermal shock data” is corrupted Pressing RESET will restore factory default values
e332 NO FAULT HISTRY DATA Stored “fault history data” is corrupted Pressing RESET will restore factory default values
e333 NO SETBACK DATA Stored “setback data” is corrupted Pressing RESET will restore factory default values
e334 NO COMM SETUP DATA Stored “communication data” is corrupted Pressing RESET will restore factory default values
e335 NO SEQUENCING DATA Stored “sequencing data” is corrupted Pressing RESET will restore factory default values
e336 NO O2 SETUP DATA Stored “o2 setup data” is corrupted Pressing RESET will restore factory default values
e337 NO ADJUSTED O2 DATA Stored “adjusted o2 data” is corrupted Pressing RESET will restore factory default values
e338 NO ANALOG OUT DATA Stored “analog out data” is corrupted Pressing RESET will restore factory default values
e339 NO VFD SETUP DATA Stored “vfd setup data” is corrupted Pressing RESET will restore factory default values
e340 NO VFD PROFILE1 DATA Stored “vfd profile 1 data” is corrupted Pressing RESET will restore factory default values
e341 NO VFD PROFILE2 DATA Stored “vfd profile 2 data” is corrupted Pressing RESET will restore factory default values
e342 NO VFD PROFILE3 DATA Stored “vfd profile 3 data” is corrupted Pressing RESET will restore factory default values
e343 NO VFD PROFILE4 DATA Stored “vfd profile 4 data” is corrupted Pressing RESET will restore factory default values
e344
to
e368
Unused Unused
e369
PPC4000 FAULT
“sensor data” is corrupted
Pressing RESET will restore values from stored
memory
e370
PPC4000 FAULT
“servo data” is corrupted
Pressing RESET will restore values from stored
memory
e371
PPC4000 FAULT
“di data” is corrupted
Pressing RESET will restore values from stored
memory
e372
PPC4000 FAULT
“passcode data” is corrupted
Pressing RESET will restore values from stored
memory
e373
PPC4000 FAULT
“p0 data” is corrupted
Pressing RESET will restore values from stored
memory
e374
PPC4000 FAULT
“profile 1 data” is corrupted
Pressing RESET will restore values from stored
memory