User`s guide
88
Error Code Displayed Reason for error Possible remedy
e89 NOT COMMISSIONED User has less than 3 points in the current profile Recommission current profile
e90
PPC4000 FAULT
FRAM chip may be bad Replace PPC4000
e91
PPC4000 FAULT
Helper CPU may not be programmed Replace PPC4000
e92
Unused Unused
e93
PPC4000 FAULT
The main and helper CPUs are not communicating Replace PPC4000
e94
PPC4000 FAULT
Helper CPU has detected an internal error Replace PPC4000
e95
PPC4000 FAULT
Helper CPU has detected an internal error Replace PPC4000
e96
PPC4000 FAULT
Helper CPU has detected an internal error Replace PPC4000
e97
PPC4000 FAULT
Helper CPU has detected an internal error Replace PPC4000
e98
PPC4000 FAULT
The main and helper CPUs are not communicating Replace PPC4000
e99
PPC4000 FAULT
Helper CPU may not be programmed properly Replace PPC4000
e100 CHECK WIRING Pin stuck-at-fault detected Replace PPC4000
e101 CHECK WIRING Pin stuck-at-fault detected Replace PPC4000
e102
PPC4000 FAULT
Helper CPU has detected an internal error Replace PPC4000
e103
to
e121
PPC4000 FAULT PPC4000 Internal Error Replace PPC4000 (notify Fireye about this error)
e122 SERVO 1 LOST Communications to the servo has stopped
Check servo address selection, check
wiring.
e123 SERVO 2 LOST Communications to the servo has stopped
Check servo address selection, check
wiring, add 200 resistor.
e124 SERVO 3 LOST Communications to the servo has stopped
Check servo address selection, check
wiring, replace servo.
e125 SERVO 4 LOST Communications to the servo has stopped
In this order: check servo address selection, check
wiring, add 200 resistor, replace servo.
e126 SERVO 5 LOST Communications to the servo has stopped
In this order: check servo address selection, check
wiring, add 200 resistor, replace servo.
e127 SERVO 6 LOST Communications to the servo has stopped
In this order: check servo address selection, check
wiring, add 200 resistor, replace servo.
e128 SERVO 7 LOST Communications to the servo has stopped
In this order: check servo address selection, check
wiring, add 200 resistor, replace servo.
e129 SERVO 8 LOST Communications to the servo has stopped
In this order: check servo address selection, check
wiring, add 200 resistor, replace servo.
e130 SERVO 9 LOST Communications to the servo has stopped
In this order: check servo address selection, check
wiring, add 200 resistor, replace servo.
e131 SERVO 10 LOST Communications to the servo has stopped
In this order: check servo address selection, check
wiring, add 200 resistor, replace servo.
e132
to
e141
Unused Unused
e142 SERVO 1 STUCK
Expected shaft movement does not equal measured
shaft movement
In this order: Excessive torque, servo hitting hard
stop, defective servo.
e143 SERVO 2 STUCK
Expected shaft movement does not equal measured
shaft movement
In this order: Excessive torque, servo hitting hard
stop, defective servo.